Four-stage gas heating is enabled when zone sensor, Discharge Air Control, or fresh air tempering mode is selected. (Available when using the CS8500 thermostat or
1
when connected to Building Automation Systems using BACnet, LonTalk, or S-Bus protocols.
HIG H ALT IT U DE D ERATE
Units may be installed at altitudes up to 610 m (2000 feet) above sea level without any modification.
At altitudes above 610 m (2000 feet), units must be derated to match gas manifold pressures shown in table below.
At altitudes above 1372 m (4500 feet) unit must be derated 2% for each 305 m (1000 feet) above sea level.
NOTE - This is the only permissible derate for these units.
Gas Heat
Altitude - m
Type
Low (L)
Standard (S)
610 - 1372
(2001 - 4500)
Medium (M)
6110 - 1372
(2001 - 4500
High (H)
6110 - 1372
(2001 - 4500
Model Number
Heat Input Type
First Stage
49.5 (169 000)
Second Stage
First Stage
39.5 (135 000)
Second Stage
First Stage
Second Stage
Third Stage
Fourth Stage
First Stage
39.5 (135,000)
Second Stage
Third Stage
Fourth Stage
8 - 25 (15 - 45)
Thermal Efficiency
Natural
LPG/Propane
Gas Manifold Pressure
(ft.)
kPa (in. w.g.)
Natural Gas
0.52 (2.6)
0.52 (2.6)
0.52 (2.6)
LGH156
LGH180
LGH210
Low (L)
Standard (S)
1
2
49.5 (169 000)
- - -
68.5 (234 000)
- - -
- - -
54.8 (187 000)
N/A
24.7 (84,500)
N/A
49.5 (169,000)
N/A
62.7 (214,000)
N/A
76.2 (260,000)
- - -
N/A
- - -
N/A
- - -
N/A
60.9 (208,000)
8 - 25 (15 - 45)
80.0%
80.0%
1 in. npt
1 in. npt
1.7 (7)
1.7 (7)
2.7 (11)
2.7 (11)
Natural Gas or LPG/Propane - kW (Btuh)
LPG/Propane Gas
First Stage
No adjustment required
1.82 (7.3)
49.5 (169 000)
1.82 (7.3)
68.5 (233 000)
1.82 (7.3)
91.4 (311 000)
Energence
Packaged Gas / Electric 45.7 to 88 kW - 50 Hz/ Page 21