Lennox Energence LGH Manual page 22

Table of Contents

Advertisement

R ATIN G S
NOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.
45.7 kW - LGH156H4 (1ST STAGE)
18.3°C
Entering
Total
Wet
Air
Total
Comp.
Bulb
Volume
Cool
Motor
Temper-
Cap.
Input
ature
L/s
kW
kW
1965
28.6
3.87
17.2°C
2455
30.3
3.9
2945
31.6
3.93
1965
30.7
3.91
19.4°C
2455
32.4
3.95
2945
33.8
3.98
1965
32.7
3.95
21.7°C
2455
34.6
3.99
2945
35.9
4.03
45.7 kW - LGH156H4 (2ND STAGE)
26.7°C
Entering
Total
Wet
Air
Total
Comp.
Bulb
Volume
Cool
Motor
Temper-
Cap.
Input
ature
L/s
kW
kW
1965
39.3
7.04
17.2°C
2455
41.6
7.09
2945
44.0
7.15
1965
42.3
7.11
19.4°C
2455
44.6
7.16
2945
46.2
7.2
1965
45.3
7.17
21.7°C
2455
47.7
7.23
2945
49.5
7.28
48°C
Entering
Total
Wet
Air
Total
Comp.
Bulb
Volume
Cool
Motor
Temper-
Cap.
Input
ature
L/s
kW
kW
1965
27.0
11.23
17.2°C
2455
29.7
11.30
2945
31.8
11.35
1965
29.4
11.29
19.4°C
2455
31.0
11.33
2945
32.2
11.37
1965
32.0
11.36
21.7°C
2455
33.8
11.41
2945
35.0
11.45
Energence
Packaged Gas / Electric 45.7 to 88 kW - 50 Hz / Page 22
®
Outdoor Air Temperature Entering Outdoor Coil
23.9°C
Sensible To Total
Total
Comp.
Ratio (S/T)
Cool
Motor
Cap.
Input
Dry Bulb
24°C 27°C 29°C
kW
kW
0.71
0.85
0.99
26.6
4.38
0.76
0.93
1.00
28.2
4.41
0.81
0.99
1.00
29.6
4.44
0.56
0.68
0.81
28.7
4.42
0.59
0.74
0.90
30.3
4.45
0.62
0.79
0.97
31.5
4.48
0.42
0.55
0.66
30.6
4.46
0.44
0.58
0.72
32.4
4.50
0.45
0.62
0.77
33.7
4.53
Outdoor Air Temperature Entering Outdoor Coil
35°C
Sensible To Total
Total
Comp.
Ratio (S/T)
Cool
Motor
Cap.
Input
Dry Bulb
24°C 27°C 29°C
kW
kW
0.74
0.91
1.00
34.6
8.43
0.81
0.99
1.00
37.1
8.48
0.87
1.00
1.00
39.4
8.54
0.57
0.72
0.87
37.5
8.49
0.61
0.79
0.96
39.5
8.54
0.65
0.85
1.00
40.9
8.58
0.41
0.56
0.70
40.3
8.56
0.43
0.60
0.77
42.5
8.62
0.45
0.64
0.83
44.0
8.66
Outdoor Air Temperature Entering Outdoor Coil
50°C
Sensible To Total
Total
Comp.
Ratio (S/T)
Cool
Motor
Cap.
Input
Dry Bulb
24°C 27°C 29°C
kW
kW
0.79
1.00
1.00
25.9
11.74
0.90
1.00
1.00
28.5
11.81
0.98
1.00
1.00
30.5
11.87
0.55
0.77
0.98
28.1
11.80
0.62
0.87
1.00
29.7
11.84
0.68
0.96
1.00
30.9
11.88
0.34
0.55
0.75
30.7
11.87
0.38
0.62
0.85
32.4
11.92
0.41
0.68
0.94
33.6
11.96
29.4°C
Sensible To Total
Total
Comp.
Ratio (S/T)
Cool
Motor
Cap.
Input
Dry Bulb
24°C 27°C 29°C
kW
kW
0.71
0.86
1.00
24.6
4.94
0.77
0.95
1.00
26.1
4.97
0.83
1.00
1.00
27.6
5.00
0.55
0.69
0.83
26.6
4.98
0.59
0.75
0.92
28.1
5.01
0.62
0.81
0.99
29.2
5.04
0.41
0.54
0.67
28.5
5.02
0.42
0.58
0.73
30.1
5.06
0.44
0.62
0.78
31.3
5.09
43.3°C
Sensible To Total
Total
Comp.
Ratio (S/T)
Cool
Motor
Cap.
Input
Dry Bulb
24°C 27°C 29°C
kW
kW
0.76
0.95
1.00
29.7
10.11
0.83
1.00
1.00
32.4
10.18
0.91
1.00
1.00
34.6
10.24
0.56
0.74
0.91
32.3
10.18
0.61
0.81
0.99
34.1
10.23
0.66
0.89
1.00
35.4
10.26
0.39
0.56
0.71
35.1
10.25
0.41
0.61
0.79
37.0
10.30
0.43
0.65
0.86
38.3
10.34
51.7°C
Sensible To Total
Total
Comp.
Ratio (S/T)
Cool
Motor
Cap.
Input
Dry Bulb
24°C 27°C 29°C
kW
kW
0.81
1.00
1.00
25.0
12.20
0.92
1.00
1.00
27.5
12.27
0.99
1.00
1.00
29.5
12.32
0.55
0.78
0.99
27.0
12.25
0.62
0.89
1.00
28.5
12.30
0.68
0.98
1.00
29.7
12.33
0.33
0.55
0.76
29.6
12.32
0.37
0.62
0.86
31.2
12.37
0.40
0.69
0.95
32.4
12.41
Sensible To Total
Total
Comp.
Ratio (S/T)
Cool
Motor
Cap.
Input
Dry Bulb
24°C 27°C 29°C
kW
kW
0.72
0.88
1.00
22.5
5.57
0.78
0.97
1.00
24.0
5.60
0.85
1.00
1.00
25.6
5.64
0.54
0.69
0.84
24.4
5.61
0.59
0.76
0.94
25.9
5.64
0.63
0.82
0.99
26.9
5.67
0.39
0.54
0.67
26.3
5.65
0.41
0.58
0.74
27.9
5.69
0.43
0.62
0.80
28.9
5.72
Sensible To Total
Total
Comp.
Ratio (S/T)
Cool
Motor
Cap.
Input
Dry Bulb
24°C 27°C 29°C
kW
kW
0.78
0.99
1.00
28.2
10.73
0.87
1.00
1.00
30.9
10.79
0.96
1.00
1.00
33.0
10.85
0.56
0.75
0.95
30.7
10.79
0.61
0.85
1.00
32.4
10.83
0.67
0.93
1.00
33.6
10.87
0.37
0.55
0.73
33.4
10.86
0.39
0.61
0.82
35.2
10.91
0.42
0.67
0.91
36.5
10.95
Sensible To Total
Ratio (S/T)
Dry Bulb
24°C 27°C 29°C
0.81
1.00
1.00
0.93
1.00
1.00
1.00
1.00
1.00
0.55
0.79
0.99
0.62
0.90
1.00
0.69
0.99
1.00
0.32
0.55
0.76
0.36
0.62
0.87
0.40
0.69
0.96
35°C
Sensible To Total
Ratio (S/T)
Dry Bulb
24°C
27°C
29°C
0.72
0.91
1.00
0.79
0.99
1.00
0.87
1.00
1.00
0.54
0.70
0.87
0.59
0.77
0.96
0.63
0.85
1.00
0.37
0.53
0.68
0.40
0.58
0.75
0.42
0.63
0.82
46°C
Sensible To Total
Ratio (S/T)
Dry Bulb
24°C
27°C
29°C
.79
.99
1.00
.89
1.00
1.00
.97
1.00
1.00
.55
.77
.97
.62
.87
1.00
.68
.95
1.00
.35
.55
.75
.38
.62
.84
.41
.68
.93

Advertisement