Daikin FTV-A Series Engineering Data page 70

Split unit air conditioner wall mounted
Table of Contents

Advertisement

Electric Characteristic
Unit Combination
Indoor Unit
Outdoor Unit
FTV28P
RV28F
FTV35P
RV35F
FTV50P
RV50C
FTV60P
RV60C
FTV85PS
RC85A
Symbols:
MCA
: Min. circuit amps (A)
MFA
: Max. fuse amps (A)
LRA
: Locked Rotor Ampere (A)
RLA
: Rated loads amps (A)
OFM
: Outdoor fan motor
IFM
: Indoor fan motor
W
: Fan motor rated output (W)
FLA
: Full load amps (A)
68
Power Supply
Hz
Volts
Voltage Range
50
220
Max. 50Hz 264V
50
230
Min. 50Hz 198V
50
240
50
220
Max. 50Hz 264V
50
230
Min. 50Hz 198V
50
240
50
220
Max. 50Hz 264V
50
230
Min. 50Hz 198V
50
240
50
220
Max. 50Hz 264V
50
230
Min. 50Hz 198V
50
240
50
220
Max. 50Hz 264V
50
230
Min. 50Hz 198V
50
240
COMP
MCA
MFA
LRA
5.84
16.0
16.0
6.44
16.0
27.9
11.60
20.0
34.0
13.10
20.0
32.0
20.2
25.0
67.0
Notes:
1. RLA is based on the following conditions.
Indoor temp. 27°CDB / 19°CWB.
Outdoor temp. 35°CDB.
2. Maximum allowable voltage variation between phases is 2%.
3. Select wire size based on the larger value of MCA.
4. Instead of fuse, use circuit breaker.
5. Be sure to install an earth leak detector.
(This unit uses an inverter, which means that an earth leak
detector capable of handling high harmonics must be used in
order to prevent malfuctioning of the earth leak detector.)
OFM
IFM
RLA
kW
FLA
kW
3.45
0.020
0.22
0.018
4.59
0.020
0.23
0.018
7.48
0.032
0.34
0.026
8.89
0.060
0.53
0.030
12.0
0.066
0.58
0.070
FLA
0.19
0.21
0.30
0.34
0.51