Indoor Setting Temperature; Outdoor Pipe Temperature/2-Phase (Th6); Outdoor Outside Temperature (Th7); Outdoor Heatsink Temperature (Th8) - Mitsubishi Electric SUZ-KA24NAHZ Service Manual

Hide thumbs Also See for SUZ-KA24NAHZ:
Table of Contents

Advertisement

SW2 setting

Indoor setting temperature

ON
62 to 86
1
2 3 4 5 6
Outdoor pipe temperature/2-phase
(TH6)
ON
−38 to 190
1
2 3 4 5 6

Outdoor outside temperature (TH7)

−38 to 190
ON
1
2 3 4 5 6

Outdoor heatsink temperature (TH8)

−40 to 327
ON
1
2 3 4 5 6
Discharge superheat. SHd
0 to 458
ON
Cooling = [Higher temperature of
Heating = [Higher temperature of
1
2 3 4 5 6
Number of defrost cycles
0 to FFFE
ON
1
2 3 4 5 6
Input current of outdoor unit
ON
1
2 3 4 5 6
LEV-B opening pulse
0 to 480
ON
1
2 3 4 5 6
U9 error detail history (latest)
ON
1
2 3 4 5 6
OCH754A
Display detail
TH4 or TH32] −TH6
TH4 or TH32] −TH5
69
The black square (■) indicates a switch position.
Explanation for display
62 to 86 [17 to 30˚C]
−38 to 190 [−39 to 88˚C]
(When the temperature is 0˚F [0˚C] or less, "–" and
temperature are displayed by turns.)
−38 to 190 (−39 to 88˚C)
(When the temperature is 0˚F [0˚C] or less, "–" and
temperature are displayed by turns.)
−40 to 327 [−40 to 164˚C]
(When the temperature is 0˚F [0˚C] or less, "–" and
temperature are displayed by turns.)
(When the thermistor detects 100˚F or more,
hundreds digit, tens digit and ones digit are
displayed by turns.)
0 to 458 [0 to 255˚C]
(When the temperature is 100˚F or more, hun-
dreds digit, tens digit and ones digit are displayed
by turns.)
0 to FFFE (in hexadecimal notation)
(When more than FF in hex (255 in decimal), the
number is displayed in order of 16
16
's and 16
's places.
1
0
Example: When 5000 cycles;
0.5 s
0 to 500
(When it is 100 or more, hundreds digit, tens digit
and ones digit are displayed by turns.)
0 to 480
(When it is 100 pulse or more, hundreds digit, tens
digit and ones digit are displayed by turns.)
Description
Normal
Overvoltage error
Undervoltage error
Input current sensor error
Abnormal power synchronous signal
PFC error
(Overvoltage/Undervoltage/Overcurrent)
• Display examples for multiple errors:
Overvoltage (01) + Undervoltage (02) = 03
Undervoltage (02) + Power-sync signal error (08) = 0A
L1 phase open error (04) + PFC error (10) = 14
's and 16
's, and
3
2
0.5 s
2 s
9
C4
Display
00
01
02
04
08
10
Unit
˚F [˚C]
˚F [˚C]
˚F [˚C]
˚F [˚C]
˚F [˚C]
2 cycles
0.1 A
Pulse
Code
display