COMBINATION OF INDOOR AND OUTDOOR UNITS Outdoor unit Indoor unit Heat pump type SUZ- Service KA25VA(H).TH KA35VA(H).TH KA50VA.TH KA60VA.TH KA71VA.TH Service Ref. Manual No. — — — — SLZ-KA25VA(L).TH — — — SLZ-KA35VA(L).TH — OC320 — — — — SLZ-KA50VA(L).TH —...
Page 3
INFORMATION FOR THE AIR CONDITIONER WITH R410A REFRIGERANT • This room air conditioner adopts an HFC refrigerant (R410A) which never destroys the ozone layer. • Pay particular attention to the following points, though the basic installation procedure is same as that for R22 conditioners. 1 As R410A has working pressure approximate 1.6 times as high as that of R22, some special tools and piping parts/ materials are required.
Page 4
Conversion chart of refrigerant temperature and pressure (MPa [Gauge]) R410A NOTE : The unit of pressure has been changed to MPa on the international system of units(SI unit system). f [Gauge]) The conversion factor is: 1(MPa [Gauge]) =10.2(kgf/f -0.5 -30 -20 -10 1.
Page 5
2 Flaring work and flare nut Flaring work for R410A pipe differs from that for R22 pipe. For details of flaring work, refer to Installation manual “FLARING WORK”. Dimension of flare nut (mm) Pipe diameter (mm) R410A 6.35 9.52 12.7 15.88 3.
PART NAMES AND FUNCTIONS SUZ-KA25VA.TH ACCESSORIES SUZ-KA35VA.TH SUZ-KA25VAH.TH SUZ-KA35VAH.TH OUTDOOR UNIT Air inlet (back and side) Piping SUZ-KA25VA(H).TH SUZ-KA35VA(H).TH Drain hose Drain socket Air outlet Drain outlet SUZ-KA50VA.TH ACCESSORIES SUZ-KA60VA.TH SUZ-KA71VA.TH OUTDOOR UNIT Air inlet (back and side) SUZ-KA50VA.TH SUZ-KA60VA.TH Piping SUZ-KA71VA.TH...
SPECIFICATION SLZ-KA•VA(L).TH / SUZ-KA•VA(H).TH SUZ-KA25VA(H).TH SUZ-KA35VA(H).TH SUZ-KA50VA.TH Indoor Service Ref. Indoor Service Ref. Indoor Service Ref. Outdoor Service Ref. SLZ-KA25VA(L).TH SLZ-KA35VA(L).TH SLZ-KA50VA(L).TH Cooling Cooling Function Cooling Heating Heating Heating Single phase Single phase Single phase Power supply 230V,50Hz 230V,50Hz 230V,50Hz Capacity Rated frequency(Min.~Max.) 2.5(0.9-3.2) 3.0(0.9-4.5)
Page 8
SEZ-KC•VA.W, SEZ-KA•VA.TH / SUZ-KA•VA(H).TH SUZ-KA25VA(H).TH SUZ-KA35VA(H).TH Indoor Service Ref. Indoor Service Ref. Outdoor Service Ref. SEZ-KC25VA.W SEZ-KA35VA.TH Cooling Heating Function Cooling Heating Single phase Single phase Power supply 230V,50Hz 230V,50Hz 2.5(0.9-3.2) 3.5(1.0-3.9) 4.0(0.9-5.0) Capacity Rated frequency(Min.-Max.) 3.0(0.9-4.5) — Dehumidification — Air flow 1 2,058 1,938...
Page 9
SEZ-KA•VA.TH / SUZ-KA•VA.TH SUZ-KA50VA.TH SUZ-KA60VA.TH SUZ-KA71VA.TH Outdoor Service Ref. Indoor Service Ref. Indoor Service Ref. Indoor Service Ref. SEZ-KA50VA.TH SEZ-KA60VA.TH SEZ-KA71VA.TH Cooling Cooling Cooling Heating Heating Heating Function Single phase Single phase Single phase Power supply 230V,50Hz 230V,50Hz 230V,50Hz 5.0(1.1-5.6) 5.5(1.1-6.3) 7.1(0.9-8.3) Capacity Rated frequency(Min.~Max.)
Page 10
Specifications and rating conditions of main electric parts SUZ-KA25VA.TH SUZ-KA25VAH.TH SUZ-KA35VA.TH SUZ-KA35VAH.TH Model SUZ-KA25VA.TH SUZ-KA25VAH.TH SUZ-KA35VA.TH SUZ-KA35VAH.TH Item (CT) Current transformer ETA19Z59BZ (CT761, CT781) Current transformer ETQ19Z71AY (C63A, C63B, C63C) Smoothing capacitor 620+ 420V (DB61, DB65) Diode module D25XB60 (F61)
NOISE CRITERIA CURVES SUZ-KA25VA.TH SUZ-KA35VA.TH SUZ-KA25VAH.TH SUZ-KA35VAH.TH FUNCTION SPL(dB(A)) FUNCTION SPL(dB(A)) FAN SPEED LINE FAN SPEED LINE COOLING COOLING High High Med. Med. HEATING HEATING Test conditions, Test conditions, Cooling : Dry-bulb temperature 35: Wet-bulb temperature (24:) Cooling : Dry-bulb temperature 35: Wet-bulb temperature (24:)
OUTLINES AND DIMENSIONS SUZ-KA25VA.TH SUZ-KA25VAH.TH Unit: mm SUZ-KA35VA.TH SUZ-KA35VAH.TH OUTDOOR UNIT REQUIRED SPACE Basically open 100mm or more without any obstruction in front and on both sides of the unit. Drain hole [42 (SUZ-KA25/KA35VA) Drain hole [33 (SUZ-KA25/KA35VAH) Air in...
Page 13
SUZ-KA50VA.TH Unit: mm SUZ-KA60VA.TH SUZ-KA71VA.TH OUTDOOR UNIT REQUIRED SPACE Open as a rule 500mm or more if the front and both sides are open 100mm or more 200mm or more if 100mm or more there are obstacles to both sides Open as a rule 500mm or more if the back, 350mm or more...
PERFORMANCE CURVES SLZ-KA25VA(L).TH / SUZ-KA25VA.TH, SUZ-KA25VAH.TH SLZ-KA35VA(L).TH / SUZ-KA35VA.TH, SUZ-KA35VAH.TH SLZ-KA50VA(L).TH / SUZ-KA50VA.TH The standard data contained in these specifications apply only to the operation of the air conditioner under normal condition. Operating conditions vary according to the areas where these units are installed. The following information has been provided to clarify the operating characteristics of the air conditioner under the conditions indicated by the performance curve.
Page 23
20.8 23.9 28.2 22.1 19.2 26.0 17.6 20.2 23.9 16.0 18.4 21.7 14.4 16.5 19.5 12.8 14.7 17.4 11.2 12.9 15.2 11.0 13.0 Outdoor intake air Wet-bulb temperature (:) Outdoor intake air Wet-bulb temperature (:) NOTE:The above curves are for the heating operation without any frost. SUZ-KA25VA(H).TH SUZ-KA25VA(H).TH SUZ-KA25VA(H).TH...
OUTDOOR LOW PRESSURE AND OUTDOOR UNIT CURRENT COOL operation Relative humidity(%) Dry-bulb temperature 1 Both indoor and outdoor unit are under the same temperature/humidity condition. 2 Air flow : High speed 3 Operational frequency : 58Hz(SUZ-KA25VA(H).TH) 73Hz(SUZ-KA35VA(H).TH) 75Hz(SUZ-KA50VA.TH) SUZ-KA35VA(H).TH SUZ-KA50VA.TH SUZ-KA25VA(H).TH (kgf/F [Gauge]) (MPa [Gauge])
SEZ-KC25VA.W / SUZ-KA25VA.TH, SUZ-KA25VAH.TH SEZ-KA35VA.TH / SUZ-KA35VA.TH, SUZ-KA35VAH.TH SEZ-KA50VA.TH / SUZ-KA50VA.TH SEZ-KA60VA.TH / SUZ-KA60VA.TH SEZ-KA71VA.TH / SUZ-KA71VA.TH The standard data contained in these specifications apply only to the operation of the air conditioner under normal condition. Operating conditions vary according to the areas where these units are installed. The following information has been provided to clarify the operating characteristics of the air conditioner under the conditions indicated by the performance curve.
Page 26
Cooling capacity Total input (cooling) Outdoor intake air Dry-bulb temperature (:) Outdoor intake air Dry-bulb temperature (:) Cooling capacity Total input (cooling) 10.5 Outdoor intake air Dry-bulb temperature (:) Outdoor intake air Dry-bulb temperature (:) Heating capacity Total input (heating) 25.2 22.7 24.5...
Page 27
SUZ-KA25VA(H).TH SUZ-KA25VA(H).TH SUZ-KA25VA(H).TH SUZ-KA25VA(H).TH Correction of Cooling capacity Correction of Cooling total input Correction of Heating total input Correction of Heating capacity 150(Hz) 150(Hz) 150(Hz) 150(Hz) The operational frequency of compressor The operational frequency of compressor The operational frequency of compressor The operational frequency of compressor SUZ-KA35VA(H).TH SUZ-KA35VA(H).TH...
Page 28
OUTDOOR LOW PRESSURE AND OUTDOOR UNIT CURRENT <How to operate fixed-frequency operation (Test run operation)> 1. Press the TEST button to COOL or HEAT mode. 2. Test run operation starts and continue to operate for 30 minutes. 3. Compressor starts at rated frequency in COOL mode or 58Hz in HEAT mode. 4.
<COOL> <HEAT> 5 seconds 5 seconds Compressor R.V.coil ON or OFF ON or OFF Outdoor fan motor 10-3. Relation between main sensor and actuator SUZ-KA25VA.TH SUZ-KA35VA.TH SUZ-KA25VAH.TH SUZ-KA35VAH.TH Actuator Sensor Purpose Outdoor Indoor Defrost Compressor RV-coil fan motor fan motor...
SUZ-KA35VAH.TH soldered (Initial setting) none (cut) TROUBLESHOOTING SUZ-KA25VA.TH SUZ-KA35VA.TH SUZ-KA25VAH.TH SUZ-KA35VAH.TH SUZ-KA50VA.TH SUZ-KA60VA.TH SUZ-KA71VA.TH 12-1. Cautions on troubleshooting 1. Before troubleshooting, check the following: 1) Check the power supply voltage. 2) Check the indoor/outdoor connecting wire for mis-wiring. 2. Take care the following during servicing.
Page 50
E02 444 705 DRAIN CAP HEAD OFFICE: MITSUBISHI DENKI BLDG., 2-2-3, MARUNOUCHI, CHIYODA-KU, TOKYO100-8310, JAPAN cCopyright 2005 MITSUBISHI ELECTRIC ENGINEERING CO.,LTD New publication, effective Oct. 2005 Distributed in Oct. 2005. No.OC322 REVISED EDITION-A PDF 8 Specifications subject to change without notice Distributed in Apr.