Minimum Height Of Flue System Exit - Quadra-Fire 21M-ACC-NZ Installation Manual

2100 millennium new zealand wood appliance automatic combustion control (acc)
Hide thumbs Also See for 21M-ACC-NZ:
Table of Contents

Advertisement

B. Minimum Height of Flue System Exit
3000mm
increase as necessary until nothing
within 3000mm of fluetop
any nearby structure
Figure 11.1
NOTICE:
Chimney performance may vary.
Trees, buildings, roof lines and wind conditions affect
performance.
Chimney height may need adjustment if smoking or
overdraft occurs.
October 23, 2018
3000mm
more than 3000mm
or less
600mm
minimum
Locating the appliance in a basement or in a location
of considerable air movement can cause intermittent
smoke spillage from appliance. Do not locate
appliance near
Frequently open doors
Central heat outlets or returns
7039-186A
2100 Millennium NZ Wood Appliance
3000mm
increase from
1000mm minimum
until clear within
3000mm of flue top
NOTICE:
11

Advertisement

Table of Contents
loading

Table of Contents