Minimum Height Of Flue System Exit - Quadra-Fire 57ST-ACC-AU Installation Manual

5700 step top australia wood appliance automatic combustion control (acc)
Table of Contents

Advertisement

B. Minimum Height of Flue System Exit
3000mm
increase as necessary until nothing
within 3000mm of fluetop
any nearby structure
Figure 11.1
NOTICE:
Chimney performance may vary.
Trees, buildings, roof lines and wind conditions affect
performance.
Chimney height may need adjustment if smoking or
overdraft occurs.
16 August, 2018
3000mm
more than 3000mm
or less
600mm
minimum
Locating the appliance in a basement or in a location
of considerable air movement can cause intermittent
smoke spillage from appliance. Do not locate
appliance near
Frequently open doors
Central heat outlets or returns
7038-248A
5700 Step Top AU Wood Appliance
3000mm
increase from
1000mm minimum
until clear within
3000mm of flue top
NOTICE:
11