Operating Faults - Riello 40 FS8 Installation, Use And Maintenance Instructions

Forced draught gas burners one-stage operation
Table of Contents

Advertisement

Faults
The burner locks out during the
pre-purge phase.
The burner continues to re-
peat the starting cycle without
going on lockout.
8.2

Operating faults

Fault
The burner locks out during op-
eration.
Burner shut down.
Faults - Possible causes - Solutions
Possible Causes
The air pressure switch does not change over
to the operational position.
The flame exists.
The gas pressure in the gas-mains lies very
close to the value to which the gas pressure
switch has been set.
The sudden drop in pressure when the valve is
opened provokes the opening of the pressure
switch itself, so the valve closes again immedi-
ately and the motor stops.
The pressure then starts to increase again, the
pressure switch closes, the start-up cycle be-
gins again and so on.
Possible Causes
Earth probe.
The flame disappears 4 times.
Air pressure switch opening.
Gas pressure switch opening.
Solution
The pressure switch is faulty, change it.
The air pressure is too low, (the head is bad adjust-
ed).
Faulty valves: replace them.
Lower and set the pressure switch.
Solution
Check the right position and if necessary set it ac-
cording to the instructions of this manual.
Clean or replace the ionisation probe.
Check the gas pressure in the network and/or ad-
just the solenoid valve according to the instruc-
tions of this manual.
The air pressure is too low, (the head is bad adjust-
ed).
The air pressure switch is faulty: change it.
Check the pressure in the network and/or adjust
the solenoid valve according to the instructions of
this manual.
29
GB
Tab. K
Tab. L