5.6

Securing the burner to the boiler

Provide an adequate lifting system of the burner.
5.6.1

Hinge installation

Install the hinge 4), supplied as standard, as shown in Fig. 8.
S7392
5.7

Positioning the probe - electrode

Do not turn the ignition electrode but leave it as
shown in Fig. 10.
If the ignition electrode is put near the ionisation
WARNING
probe, the control box amplifier might be dam-
aged.
~
Probe
D5070
20063692
4
Probe
40 mm
Diffuser
Installation
 Separate the combustion head assembly from the burner
body by removing nut 1) and removing the group A)(Fig. 9).
 Fix the group B)(Fig. 9) to the boiler plate 2), inserting the
supplied insulating gasket 3).
The seal between burner and boiler must be
airtight.
WARNING
Fig. 8
A
Respect the positions shown in Fig. 10.
WARNING
Electrode
2.2
14
GB
1
3
D5108
B
Electrode
2.5 - 3.5 mm
Fig. 10
2
Fig. 9

Hide quick links: