Boiler Plate; Securing The Burner To The Boiler - Riello RS 160/E Installation, Use And Maintenance Instructions

Forced draught gas burners
Table of Contents

Advertisement

4.5

Boiler plate

Make holes in the plate shutting off the combustion chamber, as il-
lustrated in Fig. 11.
The position of the threaded holes can be marked using the ther-
mal insulation screen supplied with the burner.
 For boilers with front flue passes 13)(Fig. 12) or flame inver-
sion chambers, a protection in refractory material 11) must be
inserted between the boiler refractory 12) and the blast
tube 10).
This protection must not compromise the extraction of the
blast tube.
 For boilers with a water-cooled frontal, a refractory lining is not
necessary 11)-12)(Fig. 12) unless expressly requested by the
boiler manufacturer.
4.6

Securing the burner to the boiler

 Secure the burner to the boiler, fixing the flange 9)(Fig. 12) to
the boiler plate and interposing the insulating gasket 8).
 Use the 4 screws supplied, with a tightening torque of 26-
29 Lbf. ft, after protecting their thread with anti-seize products.
 After the start-up, check there is no leakage of flue gases into
the external environment.
D10443
Installation
1
2
15
3
19
inch
A
1
RS 160/E
9
/
16
The seal between burner and boiler must be air-
tight.
WARNING
9
4"
5
3
4
GB
D455
B
25
1
12
- 14
/
/
32
2
12
11
13
8
13
Fig. 11
C
5
W
/
8
Tab. I
Fig. 12
20069791

Advertisement

Table of Contents
loading

This manual is also suitable for:

20068988

Table of Contents