UTICA BOILERS UCS-380 Installation, Operation & Maintenance Manual page 84

Condensing gas fired floor or wall mounted boiler
Table of Contents

Advertisement

13 - TROUBLE SHOOTING
Troubleshooting Chart 9
E40 - HRU/URC Unit test error
Is HRU terminal being used
on the auxiliary SCU board
(see section 8) ?
NO
YES
Is wiring connection to HRU
Is wiring connection from
terminal secure?
SCU board to main board
secure?
NO
NO
YES
YES
Fix Wiring
Fix Wiring
Is Parameter P42 set
Connection
Connection
to 1?
NO
YES
Is P42 parameter set
to 0?
Set P42 to 1
NO
YES
OK
Not OK
Set P42 to 0
Replace SCU board
OK
NOT OK
NOT OK
Done
OK
Done
Done
Replace Main
Control Board
Is HRU accessory
operating properly?
NO
YES
Correct HRU
Accessory
84
P/N 240011662, Rev. D [06/30/2017]