Deaeration Function - UTICA BOILERS UCS-380 Installation, Operation & Maintenance Manual

Condensing gas fired floor or wall mounted boiler
Table of Contents

Advertisement

9.6 Deaeration Function

Control performs the Deaeration function at initial
Note
start and after a reset of a locking error and after
power up.
Before starting boiler deaeration function must be performed.
Rotate black cap on deaerator, located on the top of the boiler,
counter clockwise  to ensure areator is open.
• When power is supplied to the boiler Deaeration function
starts.
• Display shows 17 (Deaeration) and water pressure
(Psi). See Figure 9-4.
• Boiler pump will run on and off for up to 10 minutes.
This will purge air from the system.
• The burner will switch on for a few seconds to verify
increasing temperature on flow/return sensors.
• Boiler is ready to start in standard operation.
Repeat Deaeration function at least 3 times switching boiler on
off using
button.
9 - START UP PROCEDURE
FIGURE 9-3 AERATOR
AERATOR - LOCATED ON TOP OF BOILER
FIGURE 9-4 Deaeration Function Display Readout
Pump OFF
54
Pump ON
P/N 240011662, Rev. D [06/30/2017]