UTICA BOILERS UCS-380 Installation, Operation & Maintenance Manual page 59

Condensing gas fired floor or wall mounted boiler
Table of Contents

Advertisement

Parameters Settings - Continued
Parameter
P27
P28
P29
P30
P31
P32
P33
P34
P35
P36
P37
P38
P39
P40
P41
P42
P43
P44
P45
P46
9 - START UP PROCEDURE
Description
Clima point heating curve
outside temperature (Only
with an outdoor temperature
sensor)
Pump control, CH minimum
speed
Pump control, CH maximum
speed
Minimal outside temperature
for frost protection
Legionella protection calorifier
Set point raise at warming up
calorifier
Switch on hysteresis calorifier
sensor
3 way valve stand by: CH or
DHW
Boiler type and control type
Function of blocking input
Function of release input
Wait time for valid release
signal
Wait time for flue gas valve
Position from alarm/operation
signal relays
Minimum gas pressure
detection
HRU connected
Mains L-N phase detection
activated
Service notification for boiler
dependent maintenance
Service hours for boiler
connected to mains supply
Service hours for boiler
burner
Adjustment Range
-22 to 32ºF
-30 to 0ºC
241= 5ºF/-15ºC
2 - 10 (x 10 % )
2 - 10 (x 10 % )
-22 to 32º
-30 to 0ºC
246= 14ºF/-10ºC
0 = No
1 = Yes
2 = Controller
32 to 77ºF
0 to 25ºC
35.6 to 59ºF
2 to 15ºC
0 = CH
1 = DHW
0 = Solo (+boiler)
1 = Process heat
0 = CH enable
1 = Blocking without
frost protection
2 = Blocking with frost
protection
3 = Lock-out with frost
protection
0 = DHW enable
1 = Burner release
0 to 255 seconds 0 = No check
0 to 255 seconds
0 = Operation signal
1 = failure signal
0 = no
1 = yes
0 = no
1 = yes
0 = No
1 = Yes
0 = Off
1 = ABC
2 = Custom
1 to 255 (x 100h)
1 to 255 (x 100h)
59
Factory Setting
UCS-380
241
7
10
246
1
68ºF/20ºC
41ºF/5ºC
0
0
1
1
0
0
1
0
0
0
0
175
30
P/N 240011662, Rev. D [06/30/2017]