Gas Supply; Air Supply; Ventilation; Condensate Drain - Biasi GARDA PLUS HE M110B.24SM/E User Manual And Installation Instructions

Table of Contents

Advertisement

of the balcony
** Consideration should be given to adding
protection against condensate to the adja-
cent structure
*** Wall terminals with horizontal discharge
less than 2.5 m from a car parking space
and less than 2,1 m above the ground.
Wall terminals less than 2,1 m above the
ground with horizontal discharge of the
flue products across a public footway, or a
frequently used private access route, or a
patio (hard surface area).
5.4

Gas supply

The Gas meter is connected to the service
pipe by the local gas region or a local gas re-
gion contractor.
If the gas supply for the boiler serves other
appliances ensure that an adequate supply is
available both to the boiler and the other ap-
pliance when they are in use at the same time.
Pipework must be of adequate size. Pipes of
a smaller size than the boiler inlet connection
should not be used.
Installation pipes should be fitted in accord-
ance with BS 6891 and the complete installa-
tion should be tested for tightness.
For Ireland (IE), refer to I.S.813.2002.
5.5

Air supply

The room in which the boiler is installed does
not require a purpose provided air vent.
5.6

Ventilation

If installed in a cupboard or compartment, it is
not necessary to provide additional ventilation
for cooling for this particular product. However
consideration must be given to clearance re-
quirements for maintenance (section "Precau-
- 32 -
- 32 -
GENERAL REQUIREMENTS
tions for installation" to page 36) and under
no circumstances must stored articles be al-
lowed to come into contact with the boiler or
flue pipe.
5.7

Condensate drain

Ensure that the condensate discharge com-
plies with the national or local regulations in
force. The condensate pipe must be fitted in
accordance with Building Regulations.
Drain pipe material should be resistant to acid
as the condensate is slightly acid with a pH
less than 6.5. The boiler includes a trap (32on
page 24) that prevents the combustion prod-
ucts entering the drain.
The boilers incorporate a condensate trap with
a 75 mm seal to comply with BS6798.2000.
The schematic diagrams of possible connec-
tions are given in Fig. 5.2 and Fig. 5.3. The
length of the condensate pipe should be kept
to a minimum, any external pipe should not be
more than 3 m in 32 mm pipe and insulated to
prevent freezing.
To avoid condensate being trapped:
• the drain pipe should be run with a fall of at
least 2.5° (45 mm/m) away from the boiler;
• the number of bends and joints should be
kept at minimum;
• the drain pipe should be adequately fixed to
prevent pipe sagging.
If a part of the drainpipe runs externally this
part should be kept as short as possible and
protected to reduce the risk of freezing.

Advertisement

Table of Contents
loading

This manual is also suitable for:

Garda plus he m110b.32sm/e

Table of Contents