Three−Minute Minimum On Time; Equipment On Indicators; Heat/Cool Setpoints (Desired Temperature); Auto Changeover - Bryant PREFERRED T6-NAC Installation Instructions Manual

Preferred series ac/hp thermostat
Hide thumbs Also See for PREFERRED T6-NAC:
Table of Contents

Advertisement

S
Detect that defrost is in progress and energize the auxiliary heat to
provide homeowner comfort during the defrost cycle
S
Allow a defrost cycle to run to completion regardless of the system
demand
Three−Minute Minimum on Time
In normal operation, when a stage turns on, it will not turn off for a minimum of
3 minutes. If the setpoint is changed, this timer is canceled, allowing the
equipment to turn off immediately when the demand is removed.

Heat/Cool Setpoints (Desired Temperature)

A minimum difference of 1_ and maximum of 6_ is enforced between heating
and cooling desired temperatures. This is done by allowing 1 setting to "push"
the other, to maintain this difference. This difference is adjustable via
Configuration Option 11.

Equipment On Indicators

When cooling equipment is on, a COOL ON icon is displayed. While cooling
equipment operation is delayed by the timeguard or cycle timer, COOL ON will
flash. The same is true for HEAT ON.
During second stage compressor operation a "2" will be displayed with the
HEAT ON or COOL ON icon. This is displayed when the thermostat is
configured as H2, A2, or h2.
When the W is energized in a heat pump, the auxiliary heat on icon will be
displayed.

Auto Changeover

When auto changeover mode is selected, a change from heat to cool (or vice
versa) will not occur until an opposite mode demand has existed for 20 minutes.
If setpoint is changed, 20−minute requirement is deleted.
43