Clear Command [M8031 And M8032]; Memory Hold Stop [M8033] (Output Holding In Stop Mode); All Output Disable Command [M8034] - Mitsubishi Electric MELSEC-Q Structured Programming Manual

Hide thumbs Also See for MELSEC-Q:
Table of Contents

Advertisement

FXCPU Structured Programming Manual
[Device & Common]

4.2.12 Clear command [M8031 and M8032]

For all devices (image memory) in the PLC, the non-latched area or latched area can be cleared.
M8031 (Non-latched memory all clear)
M8032 (Latched memory all clear)
Device number
*1
M8031
(Non-latched memory all clear)
M8032
(Latched memory all clear)
*1.
In FX
/FX
3G
changed to the latched type are handled as devices in the latched area.

4.2.13 Memory hold stop [M8033] (Output holding in STOP mode)

When the special auxiliary relay M8033 is set to ON, the output status in the RUN mode is held even if the
PLC mode switches from RUN to STOP.
1. Program example
Command input
M8033
For example, when a heater is driven by the PLC, it is possible to stop the PLC while the heater and other
equipment are kept driven, change the program, an then restart the PLC again.

4.2.14 All output disable command [M8034]

When M8034 is set to ON, the output memory is cleared. As a result, contacts of all output relays are turned
OFF, and the PLC runs on the image memory.
1. Program example
Command input
M8034
4.2 Supplement of Special Devices (M8000 and later and D8000 and later)
Contact image of output relay (Y), general type auxiliary relay (M) and general type state relay (S)
Contact and time counting coil of timer (T)
Contact, number counting coil and reset coil of general type counter (C)
Current value of general type data register (D) (Except data registers used as file registers)
Current value register of timer (T)
Current value register of general type counter (C)
Contact image of latched type auxiliary relay (M) and latched type state relay (S)
Contact and time counting coil of retentive type timer (T)
Contact, number counting coil and reset coil of latched type counter and high speed counter
Current value register of latched type data register (D)
Current value of general type data register (D) (Data registers used as file registers)
Current value register of retentive type timer (T) and 1ms timer (T)
Current value register of latched type counter and high speed counter
Latched type extension register (R)
PLCs equipped with an optional battery, general-type devices which have been
3GC
Output holding in STOP mode
All outputs are disabled. (RUN mode on the image memory)
4 Operations of Special Devices (M8000 and later, D8000 and later)
Cleared devices
1
2
3
4
5
6
7
231