[Device & Common]
6.6.2

Network parameter

The following network parameter can be set in parameter setting.
• CC-Link
The CC-Link parameter is available in FX
or later.
1. In the project view, double-click [Parameter] - [Network Parameter] - [CC-Link].
Set item
Connection Block
Special Function Block No.
Operation Setting
Type
Master Station Data Link Type
Mode
Total Module Connected
Retry Count
Automatic Reconnection Station
Count
PLC Down Select
Station Information Setting
Remote Device Station Initial
Setting
298
/FX
PLCs Ver. 3.10 or later and FX
3U
3UC
Select "Set" to set a CC-Link master block.
Specify the special block number (0 to 7).
This button displays the "Operation Setting" dialog box.
This setting is fixed to "Master Station" when "Set" is selected for "Connection Block".
This setting is fixed to "PLC Parameter Auto Start" when "Set" is selected for "Connection Block".
Select the mode among the following choices:
Remote Net (Ver.1 Mode)
Remote Net (Ver.2 Mode)
Remote Net (Additional Mode)
Set the total number of remote I/O stations, remote device stations, and/or intelligent device
stations (including reserve stations) connected to the master station.
Set the number of retries in case a communication error occurs.
Set the number of remote I/O stations, remote device stations, and/or intelligent device stations
that can be returned to the system in one link scan.
Select the data link status when an error occurs in the programmable controller CPU on the
master station.
This button displays the "CC-Link Station Information" dialog box.
This button displays the "Remote Device Station Initial Setting Target Station No. Setting" dialog
box.
6 Types and Setting of Parameters
6.6 Parameter setting by GX Works2
/FX
3G
Contents of setting
PLCs Ver. 2.00
3GC