Bryant COMMERCIAL SINGLE PACKAGE ROOFTOP GAS HEAT/ELECTRIC COOLING 581B User Manual page 39

Durapac plus series sizes 036-150 commercial single package rooftop gas heat/electric cooling units
Hide thumbs Also See for COMMERCIAL SINGLE PACKAGE ROOFTOP GAS HEAT/ELECTRIC COOLING 581B:
Table of Contents

Advertisement

581B120 (10 TONS) — STANDARD AND HIGH-STATIC MOTOR
AIRFLOW
0.2
(Cfm)
Rpm
Bhp
Rpm
3000
478
0.57
658
3100
500
0.62
669
3200
519
0.69
680
3300
537
0.77
692
3400
561
0.86
704
3500
592
0.98
715
3600
632
1.12
727
3700
677
1.20
748
3800
691
1.28
761
3900
705
1.37
773
4000
720
1.47
786
4100
734
1.56
800
4200
749
1.66
813
4300
764
1.77
826
840
4400
779
1.88
854
4500
793
1.99
4600
808
2.11
868
4700
822
2.24
882
4800
837
2.37
896
4900
852
2.51
910
5000
867
2.65
924
LEGEND
Bhp
— Brake Horsepower Input to Fan
FIOP — Factory-Installed Option
NOTES:
1. Boldface indicates field-supplied drive required. (See Note 3.)
2.
indicates high static motor and drive required.
3. Motor drive range is 860 to 1080 rpm for standard motors and 830 to 1130 for
high-static motors. All other rpms require a field-supplied drive.
581B150 (12
/
TONS) — STANDARD MOTOR
1
2
AIRFLOW
0.2
(Cfm)
Rpm
Bhp
Rpm
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
868
4700
882
4800
896
4900
910
5000
867
2.65
924
5100
882
2.79
938
5200
896
2.95
952
5300
911
3.11
967
5400
926
3.27
981
5500
940
3.44
995
5600
955
3.62
1010
5700
970
3.80
1024
5800
985
3.99
1039
5900
1000
4.18
1053
6000
1015
4.39
1068
6100
1030
4.59
1083
6200
1046
4.81
LEGEND
Bhp — Brake Horsepower Input to Fan
FIOP — Factory-Installed Option
NOTES:
1. Boldface indicates field-supplied drive required. (See Note 2.)
2. Standard drive range is 900 to 1260 rpm.
3. Values include losses for filters, unit casing, and wet coils. See page 40 for
accessory/FIOP static pressure information.
PERFORMANCE DATA (cont)
FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont)
EXTERNAL STATIC PRESSURE (in. wg)
0.4
0.6
0.8
Bhp
Rpm
Bhp
Rpm
Bhp
0.92
721
1.08
796
1.23
0.97
731
1.16
808
1.30
1.03
741
1.23
818
1.38
1.10
751
1.30
828
1.47
1.17
761
1.37
837
1.57
1.24
773
1.45
847
1.66
1.32
784
1.54
857
1.76
1.43
810
1.65
869
1.89
1.52
822
1.75
880
1.98
1.62
834
1.86
891
2.08
1.71
847
1.97
902
2.19
1.82
860
2.09
914
2.31
1.92
873
2.21
926
2.44
886
2.33
938
2.57
2.04
2.16
899
2.46
951
2.71
2.28
912
2.59
963
2.86
2.42
925
2.73
975
3.00
2.56
937
2.86
988
3.16
2.71
950
3.00
1001
3.32
2.86
963
3.15
1014
3.48
3.01
977
3.30
1027
3.65
EXTERNAL STATIC PRESSURE (in. wg)
0.4
0.6
0.8
Bhp
Rpm
Bhp
Rpm
Bhp
869
1.89
880
1.98
891
2.08
902
2.19
860
2.09
914
2.31
873
2.21
926
2.44
886
2.33
938
2.57
899
2.46
951
2.71
912
2.59
963
2.86
2.42
925
2.73
975
3.00
2.56
937
2.86
988
3.16
2.71
950
3.00
1001
3.32
2.86
963
3.15
1014
3.48
3.01
977
3.30
1027
3.65
3.17
990
3.46
1040
3.82
3.33
1003
3.63
1053
4.00
3.50
1017
3.80
1066
4.18
3.68
1030
3.98
1079
4.35
3.86
1044
4.17
1092
4.54
4.04
1058
4.38
1105
4.73
4.23
1072
4.59
1118
4.93
4.42
1086
4.80
1131
5.14
4.62
1100
5.02
4.83
1114
5.25
5.04
1.0
1.2
Rpm
Bhp
Rpm
Bhp
Rpm
851
1.50
898
1.78
942
861
1.57
907
1.86
951
873
1.65
916
1.95
960
884
1.72
925
2.03
969
896
1.82
934
2.12
978
907
1.92
945
2.22
987
917
2.03
957
2.32
996
928
2.17
984
2.43
1036
937
2.28
993
2.55
1046
947
2.39
1002
2.66
1055
957
2.50
1011
2.79
1064
967
2.60
1021
2.91
1072
978
2.71
1030
3.04
1081
989
2.83
1040
3.18
1090
1000
2.96
1050
3.31
1100
1012
3.09
1061
3.43
1109
1024
3.25
1071
3.56
1119
1036
3.42
1082
3.70
1129
1048
3.59
1093
3.86
1139
1060
3.76
1105
4.02
1150
1073
3.94
1117
4.20
1161
4. Values include losses for filters, unit casing, and wet coils. See page 40 for
accessory/FIOP static pressure information.
5. Maximum continuous bhp is 3.70 for standard motors and 5.25 for high-static
motors. Extensive motor and electrical testing on these units ensures that the
full range of the motor can be utilized with confidence. Using your fan motors
up to the ratings shown will not result in nuisance tripping or premature motor
failure. Unit warranty will not be affected. See Evaporator-Fan Motor Data
tables on pages 41 and 42 for additional information.
6. Use of a field-supplied motor may affect wire sizing. Contact your Bryant
representative to verify.
1.0
1.2
Rpm
Bhp
Rpm
Bhp
Rpm
928
2.17
984
2.43
1036
937
2.28
993
2.55
1046
947
2.39
1002
2.66
1055
957
2.50
1011
2.79
1064
967
2.60
1021
2.91
1072
978
2.71
1030
3.04
1081
989
2.83
1040
3.18
1090
1000
2.96
1050
3.31
1100
1012
3.09
1061
3.43
1109
1024
3.25
1071
3.56
1119
1036
3.42
1082
3.70
1129
1048
3.59
1093
3.86
1139
1060
3.76
1105
4.02
1150
1073
3.94
1117
4.20
1161
1085
4.12
1129
4.40
1172
1098
4.30
1141
4.60
1183
1111
4.50
1153
4.80
1194
1124
4.70
1166
5.01
1137
4.91
1178
5.22
1150
5.12
4. Maximum continuous bhp is 5.25 for the standard motor. Extensive motor and
electrical testing on these units ensures that the full range of the motor can be
utilized with confidence. Using your fan motors up to the ratings shown will not
result in nuisance tripping or premature motor failure. Unit warranty will not be
affected. See Evaporator-Fan Motor Data table on pages 41 and 42 for addi-
tional information.
5. Use of a field-supplied motor may affect wire sizing. Contact your Bryant
representative to verify.
6. Interpolation is permissible. Do not extrapolate.
39
1.4
1.6
1.8
Bhp
Rpm
Bhp
Rpm
Bhp
2.01
983
2.17
1023
2.46
2.09
992
2.24
1031
2.51
2.18
1000
2.32
1039
2.58
2.27
1009
2.41
1048
2.66
2.36
1018
2.51
1057
2.75
2.46
1027
2.60
1066
2.85
2.55
1036
2.71
1075
2.96
2.68
1080
2.90
1114
3.07
2.81
1092
3.05
1129
3.25
2.94
1102
3.20
1143
3.42
3.07
1112
3.34
1155
3.59
3.20
1121
3.49
1165
3.76
3.34
1130
3.64
1175
3.92
3.48
1139
3.79
1185
4.08
3.63
1148
3.94
1194
4.25
3.78
1157
4.09
1203
4.42
3.93
1166
4.26
1212
4.58
4.09
1175
4.43
1221
4.76
4.24
1185
4.60
1230
4.93
4.38
1194
4.77
1239
5.12
4.54
1204
4.95
1.4
1.6
1.8
Bhp
Rpm
Bhp
Rpm
Bhp
2.68
1080
2.90
1114
3.07
2.81
1092
3.05
1129
3.25
2.94
1102
3.20
1143
3.42
3.07
1112
3.34
1155
3.59
3.20
1121
3.49
1165
3.76
3.34
1130
3.64
1175
3.92
3.48
1139
3.79
1185
4.08
3.63
1148
3.94
1194
4.25
3.78
1157
4.09
1203
4.42
3.93
1166
4.26
1212
4.58
4.09
1175
4.43
1221
4.76
4.24
1185
4.60
1230
4.93
4.38
1194
4.77
1239
5.12
4.54
1204
4.95
4.71
1214
5.13
4.91
5.08
2.0
Rpm
Bhp
1063
2.61
1070
2.75
1077
2.88
1086
2.95
1094
3.02
1102
3.12
1111
3.22
1135
3.17
1156
3.39
1174
3.59
1190
3.80
1203
3.99
1215
4.18
1226
4.36
1236
4.54
1246
4.72
1255
4.91
1264
5.09
2.0
Rpm
Bhp
1135
3.17
1156
3.39
1174
3.59
1190
3.80
1203
3.99
1215
4.18
1226
4.36
1236
4.54
1246
4.72
1255
4.91
1264
5.09

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Durapac plus 581b

Table of Contents

Save Article as PDF