581B048 (4 TONS) — STANDARD MOTOR
AIRFLOW
0.1
(Cfm)
Rpm
Bhp
1200
569
0.18
1300
604
0.22
1400
640
0.27
1500
676
0.32
1600
713
0.38
1700
750
0.45
1800
788
0.52
1900
826
0.60
2000
864
0.70
581B048 (4 TONS) — STANDARD MOTOR (cont)
AIRFLOW
0.9
(Cfm)
Rpm
Bhp
1200
987
0.64
1300
1006
0.71
1400
1033
0.79
1500
1060
0.88
1600
1087
1.01
1700
1114
1.07
1800
1141
1.17
1900
1168
1.28
2000
1197
1.39
581B048 (4 TONS) — HIGH-STATIC MOTOR
AIRFLOW
(Cfm)
Rpm
1200
641
1300
673
1400
705
1500
738
1600
772
1700
806
1800
841
1900
876
2000
912
581B048 (4 TONS) — HIGH-STATIC MOTOR (cont)
AIRFLOW
(Cfm)
Rpm
1200
1106
1300
1128
1400
1139
1500
1162
1600
1185
1700
1215
1800
1243
1900
1271
2000
1298
LEGEND
Bhp
— Brake Horsepower Input to Fan
FIOP — Factory-Installed Option
NOTES:
1. Boldface indicates field-supplied drive required. (See Note 3.)
2.
indicates field-supplied motor and drive required.
3. Motor drive range is 840 to 1185 rpm for standard units; 1075 to 1455 rpm for
high-static motors. All other rpms require a field-supplied drive.
4. Values include losses for filters, unit casing, and wet coils. See page 40 for
accessory/FIOP static pressure information.
PERFORMANCE DATA (cont)
FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont)
EXTERNAL STATIC PRESSURE (in. wg)
0.2
0.3
Rpm
Bhp
Rpm
641
0.23
701
673
0.28
731
705
0.33
761
738
0.38
793
772
0.44
825
806
0.51
857
841
0.59
890
876
0.68
924
912
0.77
958
EXTERNAL STATIC PRESSURE (in. wg)
1.0
1.1
Rpm
Bhp
Rpm
1030
0.70
1068
1044
0.77
1086
1069
0.86
1104
1095
0.95
1129
1123
1.05
1156
1151
1.15
1183
1178
1.26
1211
1204
1.37
1238
1231
1.48
1265
0.2
0.4
Bhp
Rpm
0.23
761
0.28
788
0.33
817
0.38
847
0.44
877
0.51
908
0.59
939
0.68
971
0.77
1004
1.2
1.4
Bhp
Rpm
Bhp
0.87
1134
0.98
0.91
1183
1.10
1.01
1218
1.14
1.09
1228
1.24
1.20
1250
1.35
1.31
1276
1.48
1.43
1303
1.61
1.56
1330
1.74
1.69
1358
1.89
0.4
Bhp
Rpm
Bhp
Rpm
0.29
761
0.34
859
0.34
788
0.39
887
0.39
817
0.45
914
0.45
847
0.51
940
0.51
877
0.58
967
0.59
908
0.66
997
0.67
939
0.75
1026
0.76
971
0.84
1056
0.86
1004
0.94
1087
1.2
Bhp
Rpm
Bhp
Rpm
0.79
1106
0.87
1134
0.84
1128
0.91
1183
0.93
1139
1.01
1218
1.02
1162
1.09
1228
1.13
1185
1.20
1250
1.23
1215
1.31
1276
1.35
1243
1.43
1303
1.47
1271
1.56
1330
1.59
1298
1.69
1358
EXTERNAL STATIC PRESSURE (in. wg)
0.6
Bhp
Rpm
Bhp
0.34
859
0.46
0.39
887
0.52
0.45
914
0.59
0.51
940
0.65
0.58
967
0.73
0.66
997
0.81
0.75
1026
0.91
0.84
1056
1.01
0.94
1087
1.12
EXTERNAL STATIC PRESSURE (in. wg)
1.6
Rpm
Bhp
1189
1.12
1226
1.23
1286
1.34
1303
1.40
1319
1.51
1334
1.64
1359
1.78
1386
1.93
1413
2.08
5. Maximum continuous bhp is 1.20 for standard motors; 2.40 for high-static
motors. Extensive motor and electrical testing on these units ensures that the
full range of the motor can be utilized with confidence. Using your fan motors
up to the ratings shown will not result in nuisance tripping or premature motor
failure. Unit warranty will not be affected. See Evaporator-Fan Motor Data
tables on pages 41 and 42 for additional information.
6. Use of a field-supplied motor may affect wire sizing. Contact your Bryant rep-
resentative to verify.
7. Interpolation is permissible. Do not extrapolate.
34
0.6
0.7
Bhp
Rpm
Bhp
0.46
901
0.52
0.52
928
0.59
0.59
955
0.66
0.65
982
0.73
0.73
1009
0.81
0.81
1037
0.90
0.91
1065
1.01
1.01
1094
1.10
1.12
1125
1.21
1.4
1.6
Bhp
Rpm
Bhp
0.98
1189
1.12
1.10
1226
1.23
1.14
1286
1.34
1.24
1303
1.40
1.35
1319
1.51
1.48
1334
1.64
1.61
1359
1.78
1.74
1386
1.93
1.89
1413
2.08
0.8
Rpm
Bhp
Rpm
943
0.58
1030
968
0.65
1044
996
0.72
1069
1024
0.81
1095
1051
0.89
1123
1077
1.01
1151
1104
1.07
1178
1132
1.18
1204
1162
1.30
1231
1.8
Rpm
Bhp
Rpm
1245
1.21
1292
1297
1.35
1346
1320
1.48
1370
1343
1.60
1393
1382
1.68
1434
1398
1.80
1451
1418
1.95
1471
1439
2.11
1493
1466
2.27
1521
0.8
Rpm
Bhp
943
0.58
968
0.65
996
0.72
1024
0.81
1051
0.89
1077
1.01
1104
1.07
1132
1.18
1162
1.30
1.8
Rpm
Bhp
1245
1.21
1297
1.35
1320
1.48
1343
1.60
1382
1.68
1398
1.80
1418
1.95
1439
2.11
1466
2.27
1.0
Bhp
0.70
0.77
0.86
0.95
1.05
1.15
1.26
1.37
1.48
2.0
Bhp
1.35
1.51
1.65
1.79
1.88
2.01
2.18
2.36
2.54