Bryant COMMERCIAL SINGLE PACKAGE ROOFTOP GAS HEAT/ELECTRIC COOLING 581B User Manual page 19

Durapac plus series sizes 036-150 commercial single package rooftop gas heat/electric cooling units
Hide thumbs Also See for COMMERCIAL SINGLE PACKAGE ROOFTOP GAS HEAT/ELECTRIC COOLING 581B:
Table of Contents

Advertisement

581B060 (5 TONS)
Temp (F)
Air Ent
Condenser
(Edb)
72
TC
70.8
75
SHC
34.1
kW
3.53
TC
68.9
85
SHC
33.5
kW
3.98
TC
66.8
95
SHC
32.8
kW
4.48
TC
64.3
105
SHC
32.0
kW
5.03
TC
61.5
115
SHC
31.0
kW
5.61
TC
58.7
125
SHC
30.0
kW
6.27
581B072 (6 TONS)
Temp (F)
Air Ent
Condenser
(Edb)
72
TC
86.7
75
SHC
43.0
kW
4.58
TC
84.1
85
SHC
42.0
kW
5.10
TC
81.3
95
SHC
41.0
kW
5.65
TC
77.9
105
SHC
39.7
kW
6.22
TC
74.7
115
SHC
38.7
kW
6.84
TC
70.3
125
SHC
37.2
kW
7.43
Standard Ratings
LEGEND
BF
— Bypass Factor
Edb — Entering Dry Bulb
Ewb — Entering Wet Bulb
kW
— Compressor Motor Power Input
SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC
— Total Capacity (1000 Btuh) Gross
PERFORMANCE DATA (cont)
COOLING CAPACITIES (cont)
Temp (F) Air Entering Evaporator — Cfm/BF
1500/0.08
Temp (F) Air Entering Evaporator — Ewb (F)
67
62
72
65.4
58.5
72.5
42.7
49.9
35.7
3.49
3.44
3.55
63.2
55.3
70.5
41.8
48.4
35.0
3.94
3.87
4.00
60.6
52.4
68.3
40.7
47.0
34.5
4.43
4.35
4.50
57.7
49.9
65.9
39.6
45.8
33.7
4.96
4.87
5.05
54.8
47.3
62.8
38.4
44.5
32.5
5.55
5.46
5.62
51.6
44.5
59.9
37.2
43.1
31.7
6.19
6.09
6.28
Temp (F) Air Entering Evaporator — Cfm/BF
1800/0.05
Temp (F) Air Entering Evaporator — Ewb (F)
67
62
72
80.7
74.4
88.8
53.7
63.8
45.0
4.46
4.33
4.63
78.2
72.0
86.4
52.6
62.7
44.5
4.97
4.85
5.16
75.3
69.2
83.4
51.4
61.4
43.4
5.52
5.39
5.71
72.0
66.1
80.0
50.2
60.0
42.2
6.08
5.94
6.29
68.4
61.8
75.9
48.8
58.1
40.8
6.68
6.49
6.87
63.6
57.2
71.8
47.0
55.8
39.5
7.25
7.03
7.48
1750/0.09
67
62
72
67.3
61.1
73.0
45.5
54.2
36.8
3.50
3.46
3.55
65.1
57.9
72.2
44.8
52.8
37.0
3.96
3.90
4.03
62.5
54.3
69.3
43.8
51.1
36.0
4.45
4.37
4.51
59.8
51.7
66.9
42.8
49.7
35.3
4.99
4.90
5.06
56.7
49.1
64.0
41.6
48.2
34.4
5.58
5.49
5.65
53.4
46.2
60.8
40.4
46.2
33.3
6.21
6.13
6.29
2100/0.06
67
62
72
82.7
76.6
90.5
57.4
68.9
47.2
4.50
4.38
4.67
80.3
74.1
88.2
56.6
68.0
46.8
5.03
4.90
5.21
77.3
71.3
85.1
55.3
66.6
45.8
5.57
5.44
5.77
73.8
68.0
81.6
54.0
65.2
44.6
6.13
6.00
6.34
70.0
64.1
77.6
52.6
63.2
43.3
6.71
6.56
6.93
65.5
59.1
72.9
51.0
59.1
41.7
7.30
7.13
7.51
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:
t
= t
ldb
edb
t
= wet-bulb temperature corresponding to enthalpy of air
lwb
leaving indoor coil (h
h
= h
lwb
ewb
Where h
ewb
3. The SHC is based on 80 F edb temperature of air entering evap-
orator coil.
Below 80 F db, subtract (corr factor x cfm) from SHC.
Above 80 F db, add (corr factor x cfm) to SHC.
Correction Factor = 1.10 x (1 – BF) x (db – 80).
19
2000/0.11
67
62
72
68.4
62.8
74.8
48.0
57.8
39.6
3.51
3.47
3.57
66.4
60.2
73.2
47.6
56.8
39.3
3.97
3.92
4.04
63.8
56.6
71.2
46.7
55.0
39.1
4.46
4.40
4.55
61.1
54.1
68.4
45.7
53.5
38.4
5.00
4.93
5.08
58.2
51.6
65.4
44.6
51.6
37.4
5.60
5.52
5.67
54.9
49.0
62.2
43.4
48.9
36.4
6.24
6.17
6.31
2400/0.06
67
62
72
84.4
78.2
92.6
61.2
73.6
51.2
4.55
4.41
4.72
81.7
75.7
90.2
60.2
72.5
50.6
5.06
4.93
5.26
78.9
72.9
87.2
59.2
71.2
50.2
5.62
5.48
5.83
75.3
69.6
83.4
57.8
69.3
49.0
6.17
6.04
6.40
71.3
66.5
78.7
56.4
66.4
46.9
6.75
6.63
6.96
66.8
61.9
74.0
55.0
61.9
45.4
7.35
7.22
7.54
sensible heat capacity (Btuh)
1.10 x cfm
)
lwb
total capacity (Btuh)
4.5 x cfm
= Enthalpy of air entering indoor coil.
2500/0.13
67
62
70.3
64.8
53.0
63.4
3.54
3.48
68.1
62.9
52.5
62.4
3.99
3.94
65.6
60.6
51.8
60.5
4.48
4.44
62.8
58.4
51.0
58.4
5.02
4.98
59.9
56.1
50.0
56.1
5.61
5.57
56.8
53.5
48.9
53.4
6.27
6.22
3000/0.08
67
62
86.3
81.0
67.4
80.7
4.58
4.47
84.0
78.8
67.4
78.7
5.12
4.99
80.6
76.2
65.8
76.2
5.66
5.55
77.1
73.2
64.5
73.2
6.22
6.12
73.0
70.1
63.2
70.0
6.80
6.72
68.6
66.4
61.8
66.3
7.41
7.33

Hide quick links: