Honeywell NOTIFIER AM-8000 Installation Manual page 16

Intelligent addressable fire detection
Hide thumbs Also See for NOTIFIER AM-8000:
Table of Contents

Advertisement

CNA terminal block
description
Phase
1
Eatrh
2
Neutral
3
CNU terminal block
Name
1
+24V USR
2
GND USR
Sounder/ Siren (positive in
3
non alarm)
Sounder/ Siren (Negative in
4
non alarm)
5
Not used
6
LIN +
7
GNDIS
8
LIN -
9
VPPLA
10
GNDP
11
CDAHA
12
GND
13
CDALA
14
VPPL1
15
GND1
16
CAN H1
17
GND
18
CAH L1
19
General Fault : NO-NC
20
General Fault : C
21
General Alarm : NO-NC
22
General Alarm : C
23
User1 : NO-NC
24
User1 : C
25
User2 : NO-NC
26
User2 : C
27
VPPLB
28
GNDP
29
CDAHB
30
GND
31
CDALB
32
VPPL2
33
GND1
34
CAN H2
35
GND
36
CAN L2
AM-8000
AM8000_manu-inst
Function
230Vac mains Power
Fused with 3,15 AL
description
Fused with 4 A fuse
Fused with 1,35A resettable fuse (this is a
(polarity inversion output
RS.485 Opto-insulated
POWER supply line
for LCD CAN bus devices
Communication line (side A)
for CAN BUS NETWORK
POWER supply line
for CAN bus AUDIO devices
Communication line (side A)
for AUDIO CAN bus devices
General Fault Relay
General Alarm Relay
User 1 Relay
User 2 Relay
POWER supply line
for CAN bus LCD devices
Communication line (side B)
for CAN BUS NETWORK
POWER supply line
for AUDIO CAN bus devices
Communication line (side A)
for AUDIO CAN bus 2
Manuale di installazione
Doc. 160.1-AM8000-ITA Rev A.3
Note
Note
EOL resistor = 47KΩ
).
NO EOL Internal resistor
Can-Bus (Output Line)
with internal EOL resistor
Power Supply line is
protected with a 4° Fuse
AUDIO 1 Line
Can-Bus with internal EOL
resistor
Power Supply line is
protected with a 4° Fuse
Contacts : 2A 30V
Normally-Open or Closed
selectable via JGST Jumper
Contacts : 2A 30V
Normally-Open or Closed
selectable via JALL Jumper
Contacts : 2A 30V
Normally-Open or Closed
selectable via JUSR1
Contacts : 2A 30V
Normally-Open or Closed
selectable via JUSR2
Can-Bus (Input Line)
with internal EOL resistor
Power Supply line is
protected with a 4° Fuse
AUDIO 2 Line
Can-Bus with internal EOL
resistor
Power Supply line is
protected with a 4° Fuse
PAGE - 13
NOTIFIER ITALIA

Hide quick links:

Advertisement

Table of Contents
loading