X520 encoder connection 1 for HTL/TTL/SSI encoder with open-circuit monitoring
Table 8- 12
Encoder connection X520
Pin
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Connector type: 15-pin sub D socket
NOTICE
Damage to motor when KTY temperature sensor is connected incorrectly
A KTY temperature sensor connected with incorrect polarity cannot detect if the motor
overheats. Overheating can cause damage to the motor.
• Connect a KTY temperature sensor with the correct polarity.
NOTICE
Damage to the encoder due to incorrect supply voltage
The encoder supply voltage can be assigned as 5 V or 24 V. Incorrect parameter
assignment can cause damage to the encoder.
• Select the appropriate supply voltage.
Cabinet Modules NEMA
Manual, 04/2014, A5E03586450A
Signal name
+Temp
Clock
Clock*
P encoder 5 V/24 V
P encoder 5 V/24 V
P sense
M encoder (M)
-Temp
M sense
R
R*
B*
B
A*/data*
A/data
8.11 K50, Sensor Module Cabinet-Mounted SMC30
Technical specifications
Motor temperature measurement KTY84-1C130 (KTY+)
Temperature sensor KTY84-1C130/PTC/
bimetallic switch with NC contact
SSI clock
Inverted SSI clock
Encoder supply
Encoder supply
Sense input, encoder supply
Ground, encoder supply
Motor temperature measurement KTY84-1C130 (KTY-)
Temperature sensor KTY84-1C130/PTC/
bimetallic switch with NC contact
Ground, sense input
Reference signal R
Inverted reference signal R
Inverted incremental signal B
Incremental signal B
Inverted incremental signal A/inverted SSI data
Incremental signal A/SSI data
Options
383