Electrical installation
4.5 Connections
Cable routing to customer terminal block -X55, frame sizes FX+FI and GX+GI
1. Feed the cable for the customer terminal block into the cabinet from the bottom right
(frame size FX+FI) or bottom left (frame size GX+GI).
2. Use cable ties to secure the cable at suitable points.
3. Feed the cable toward the top of the cabinet and, when it reaches the level of the
customer terminal block -X55, guide it to the left or right to -X55. When doing so, route
the cable in a similar manner to the standard cables that have already been installed in
the cabinet.
4. Use cable ties to secure the cable at suitable points.
5. Connect the cables to the customer terminal block -X55.
120
Frame size:
FX+FI
GX+GI
Manual, 04/2014, A5E03586450A
Cabinet Modules NEMA