Mounting And Assembly - TCS UbiquiSTAT US4010 Product Manual

Commercial bacnet thermostat
Hide thumbs Also See for UbiquiSTAT US4010:
Table of Contents

Advertisement

MOUNTING AND ASSEMBLY

1 Mounting and Assembly
The UbiquiSTAT™ is designed for wall mounting using two #6 sheet metal screws, either over a 2"x4" or 4"x4" junction
box, or directly to the wall. For best results, the thermostat should be mounted on an interior wall that represents a normal
room environment, at a height of approximately 48" from the floor. For best temperature measurement accuracy, avoid ar-
eas exposed to direct sunlight, unusual heat or cool sources, open doors and windows, unventilated locations, and hot or
cold air from diffusers. If using a remote room sensor, the sensor should be mounted in the same manner. The thermostat
should be mounted in an area which is accessible for adjusting settings.
The UbiquiSTAT consists of a base containing wiring terminal blocks and relays and a front cover containing the touch-
screen and all other circuitry. Each base and cover pair is factory calibrated and serialized together. To remove the Ubiqu-
iSTAT cover, insert a small plastic pry tool or flathead screwdriver between the front cover and base on the bottom of the
thermostat. Run the tool along the seam until the halves separate.
The following process ensures correct assembly when mating the front cover with the base. Check that no wiring inter-
feres with the cover, and no bare wires are exposed before assembly.
5
2800 Laura Ln, Middleton WI 53562 | 800.288.9383 Fax: 608.836.9044 | www.tcsbasys.com