USER INTERFACE

• Baud Rate: This defaults to 9,600 bps for TCSbus, and 38,400bps for BACnet MS/TP. All controllers on the network must
use the same baud rate (* Not shown if BACnet/IP was selected).
• Device Instance: This number must be unique across the entire BACnet network. The initial value shown is a combina-
tion of the TCS BACnet vendor ID (496) and the previously entered network address. This is done in an attempt to create
a unique value. However, users are encouraged to create their own numbering system for all controllers on the BACnet
network (* If BACnet/IP was selected, no initial value is populated in this field).
• Wi-Fi Scan Screen: If BACnet/IP was selected, this screen will show all Wi-Fi networks in range. Click Connect on the
network you wish to use.
4 User Interface

4.1 Home Screen

The home screen provides at-a-glance system information and basic user controls. The navigation automatically returns
to the home screen and the display dims after 10 minutes of inactivity (no touches detected). The basic components of
the home screen are shown below..
1. Room Temp and Setpoints: The room temperature is rounded to the nearest whole number. The currently active heat
and cool setpoints are temporarily shown in place of the room temperature when using the up/down arrows or when
the temperature value is touched. The up/down arrow raise and lower the heat and cool setpoints (User Setpoint Ad-
just) together to maintain the dead band. The up/down arrows change color (blue for cooler, orange for warmer) when
a user setpoint adjustment is active.
2. Fan Status
: This symbol is animated when the system calls for fan. Touching this symbol displays additional
information including the fan mode.
3. System State: This indicates the present operation of the controller. Touching this symbol displays additional informa-
tion including the Active System Mode (MSV-1005) and whether it is currently overridden by the network. The system
states that may be displayed on the home screen include:
a.
Flame
: Heating is active.
b.
Snowflake
: Cooling is active.
2800 Laura Ln, Middleton WI 53562 | 800.288.9383 Fax: 608.836.9044 | www.tcsbasys.com
Figure 4
14