* Permissible limits of the voltage range at which the unit will operate satisfactorily
{ If wire is applied at ambient greater than 30° C, consult table 310 ---16 of the NEC (ANSI/NFPA 70). The ampacity of non ---metallic---sheathed cable (NM),
trade name ROMEX, shall be that of 60° C conditions, per the NEC (ANSI/NFPA 70) Article 336 ---26. If other than uncoated (no ---plated), 60 or 75° C
insulation, copper wire (solid wire for 10 AWG or smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables of the NEC (ANSI/NFPA
70).
Length shown is as measured 1 way along wire path between unit and service panel for voltage drop not to exceed 2%.
}
** Time ---Delay fuse.
FLA --- Full Load Amps
LRA --- Locked Rotor Amps
MCA --- Minimum Circuit Amps
RLA --- Rated Load Amps
NOTE: Control circuit is 24 ---V on all units and requires external power source. Copper wire must be used from service disconnect to unit.
All motors/compressors contain internal overload protection.
Complies with 2001 requirements of ASHRAE Standards 90.1
A- -WEIGHTED SOUND POWER (dBA)
UNIT SIZE ---
STANDARD
SERIES
RATING
018---B
67
024---B
66
030---B
68
036---B
70
042---B
70
048---B
71
060---B
73
NOTE: Tested in accordance with ARI Standard 270 ---95. (Not listed with ARI).
CHARGING SUBCOOLING (TXV- -TYPE EXPANSION DEVICE)
OPER VOLTS*
COMPR
MAX
MIN
LRA
RLA
48.0
9.0
58.3
13.5
73.0
14.1
253
187
79.0
16.7
112.0
17.9
117.0
21.8
134.0
26.4
TYPICAL OCTAVE BAND SPECTRUM (without tone adjustment)