12.2 Soft Dry Operation

Soft Dry operation can be set using remote control.
Soft Dry operation is applied to dehumidify and to perform a gentle cooling to the room.
This operation starts when the intake air temperature sensor reaches -1.5°C from the setting temperature on the
remote control.
When operation begins, Soft Dry will be switched "ON" for a maximum 10 minutes, then Soft Dry operation will be
turned "OFF" for a minimum 6 minutes. After that, the Soft Dry operation will be "ON" and "OFF" based on the
setting temperature as shown in figure below.
However after 3 minutes of compressor off, during Soft Dry "OFF" (within 6 minutes Soft Dry restart control), the
indoor unit will start to operate at normal Cooling mode if the intake temperature is higher than Cooling "ON"
point.
Cooling OFF,
Soft Dry ON point
Soft Dry OFF point
12.2.1
Soft Dry Operation Time Diagram (For PC12TKF)
Intake
Temp
Cooling
ON
1.5°C
Set Temp
OFF
Cooling
1.0°C
Dry OFF, ON
Basic Time
Compressor
Indoor Fan
Outdoor Fan
Operation LED
<Description of operation>
a - c
c - e
e - g, i - k, m - o, v - x
g - h, l - m, o - p
t - x
Intake air
temperature
Cooling
Dry
Dry OFF
f
a
b
c
d
e
g
h
10'
6'
1'
OFF
Lo- Lo-
40º
Lo-
: Minimum 3 minutes restart control (Time Delay Safety Control) -
Cooling operation.
: 10 minutes dry operation.
: Minimum 6 minutes restart control (Time Delay Safety Control) -
Soft Dry operation.
: Minimum 60 seconds force operation.
: Freeze Prevention control.
Cooling ON point
1.5ºC
1.0ºC
Soft Dry ON point
i
j
k
l
m n
o
p
Pipe
Temp
6'
1'
6'
1'
OFF
OFF
Lo-
40º
40º
Lo-
Lo-
42
Compressor
ON
Compressor
OFF
q
r
t
s
u
v
w x
10ºC
2ºC
4'
min 6'
Lo-
Lo-
Lo-
Lo-
Operation
Stop
y
z
OFF
Lo-
40º
Lo-