TROUBLESHOOTING
Error Codes
Troubleshooting Using Error Codes - Continued
Table 23: Multi F / Multi F MAX (with or without LGRED) Outdoor Unit Error Codes.
Error
Code
21
DC Peak (IPM Fault); Compressor DC voltage was too high
22
Current Transformer2 (CT2) error; Alternating current (AC) input too high
DC Link Low Voltage (DC Link Voltage is <140VDC)
23
DC Link High Voltage (DC Link Voltage is >420VDC)
25
26
DC Compressor Position Error (Compressor failed to start properly)
27
PSC / PFC Fault; Input current to inverter compressor PCB is too high
29
32
Inverter compressor discharge pipe (D-Pipe) temperature is too high
35
Low Pressure Error; Pressure dropped below recommended limits
39
Communication Error between PFC MICOM and Inverter MICOM
40
CT Sensor Error; Thermistor is disconnected or has shorted out
41
Inverter compressor discharge pipe (D-Pipe) sensor is disconnected or has shorted out
43
High pressure sensor is disconnected or has shorted out
44
Outdoor air sensor is disconnected or has shorted out
45
Mid-pipe thermistor of outdoor unit condenser is disconnected or has shorted out
46
Outdoor unit suction piping thermistor is disconnected or has shorted out
48
Outlet piping (liquid) of condenser is disconnected or has shorted out
Combination ratio (capacity) is out of range; Total nominal indoor unit capacity is<50%
51
53
Communication failure between outdoor unit and indoor unit(s)
54
Outdoor unit is not wired properly (ex: reversed phase)
60
Outdoor unit printed circuit board (PCB) EEPROM check sum error
61
Condenser coil thermistor temperature is too high
62
Outdoor unit inverter compressor PCB heat sink temperature is too high
65
Heat sink thermistor is disconnected or has shorted out
67
Outdoor unit brushless direct current (BLDC) fan motor lock error
73
Refer to Service Manuals posted on www.lghvac.com for a full description of all error codes and workarounds.
48
Description
AC Low / High Voltage
Current to inverter compressor is too high
or >130% of the outdoor unit capacity
Outdoor unit PFC overcurrent (peak) error
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
MULTI
MULTI
No. of Times Outdoor Unit LEDs
Blink
LED01 (Red)
LED02 (Green)
2X
1X
2X
2X
2X
3X
2X
5X
2X
6X
2X
7X
2X
9X
3X
2X
3X
5X
3X
9X
4X
-
4X
1X
4X
3X
4X
4X
4X
5X
4X
6X
4X
8X
5X
1X
5X
3X
5X
4X
6X
-
6X
1X
6X
2X
6X
5X
6X
7X
7X
3X
F
F
MAX
Outdoor
Operation
Status
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Multi f maxLmcn078hvLcn098hv4Lcn128hv4Lcn188hv4

Table of Contents