Current input
Selection
CT PRIMARY
CT SECONDARY
DISPLAY RANGE
•
•
•
DISPLAY I(n)
PAC1020
Equipment Manual, 05/2020, L1V30610008B-01
CURRENT DIREC L1
CURRENT DIREC L2
CURRENT DIREC L3
7.2 Parameterizing via the operator interface
Range
Primary current of the current transformers
1 ... 99999 A
Secondary current of the current transformers
•
1 A
•
5 A
Display range setting
Freely adjustable
1 ... 99999 A
Inverse evaluation of the current flow direction
separately for each phase.
•
ON: Direction of current flow is inverted.
The device interprets the current flow direc-
tion as opposite to the wiring.
•
OFF: The device interprets the current flow
direction to match the wiring.
Display of I(n) current
•
ON: I(n) is displayed
•
OFF: I(n) is not displayed
Parameterizing
Factory
setting
50 A
5 A
50 A
OFF
ON