Siemens SENTRON PAC1020 Manual page 28

7km power monitoring device
Hide thumbs Also See for SENTRON PAC1020:
Table of Contents

Advertisement

Connection
4.1 Safety instructions
Hazardous voltage
May cause death, serious personal injury, or equipment damage.
• Always open or disconnect circuit from power-distribution system (or server) of building
• The current transformers my not be installed in equipment where they exceed
• Restrict installation of current transformers in an area where it would block ventilation
• Restrict installation of current transformers in an area of breaker arc venting.
• Not suitable for Class 2 wiring methods and not intended for connection to Class 2
• Secure current transformers and route conductors so that they do not directly contact
NOTICE
Incorrect line voltage may damage the device.
Before connecting the device, make sure that the line voltage matches the specifications on
the rating plate.
NOTICE
Short-circuit hazard
Take the maximum possible ambient temperature into account when selecting the
connecting cables.
The cables must be suitable for operation in a temperature that is 20 °C higher than the
maximum ambient temperature.
NOTICE
The direct connection of the current measuring inputs to the low-voltage system can
cause irreparable damage to the device.
The device is designed for connection to the low-voltage system via external current
transformers. Only connect the current measuring inputs to the low-voltage system via
suitable current transformers.
NOTICE
Device can be irreparably damaged
When performing an insulation test of the entire installation with AC or DC, the device
should be disconnected before starting the test.
26
WARNING
before installing or servicing current transformers.
75 percent of the wiring space of any cross-sectional area within the equipment.
openings.
equipment.
live terminals or bus.
Equipment Manual, 05/2020, L1V30610008B-01
PAC1020

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

7km1020-0ba01-1da0

Table of Contents