Connection
4.3 Connection examples
6. 3-phase measurement, 3 conductors, unbalanced load, with voltage transformer, with
2 current transformers
Connection type 3P3W
*
**
***
Figure 4-7
7. 2-phase measurement, 4 conductors, unbalanced load, without voltage transformer,
with 2 current transformers
Connection type 3P4W
*
**
***
Figure 4-8
See also
Measuring inputs (Page 13)
34
The fuses are only used for cable protection.
All commercially available miniature circuit breakers up to 20 A (C) can be used.
Connection of supply voltage
Install a short-circuit device. Protection against overvoltage when the secondary transformer
circuit is open.
Connection type 3P3W, with voltage transformer, with 2 current transformers
The fuses are only used for cable protection.
All commercially available miniature circuit breakers up to 20 A (C) can be used.
Connection of supply voltage
Install a short-circuit device. Protection against overvoltage when the secondary transformer
circuit is open.
Connection type 3P4W, without voltage transformer, with 2 current transformers
Equipment Manual, 05/2020, L1V30610008B-01
PAC1020