Figure 3: INDOOR - MOUNTING CLEARANCES (Outdoor Clearances Page 7)
NOTE: ANGLE MOUNT IS MAXIMUM 30° TO AVOID DAMAGE
Table 3: INDOOR - MINIMUM CLEARANCES TO COMBUSTIBLES
Application
INDOOR
RSEP1S25X - NG/LPG
INDOOR
RSEP1S35X - NG/LPG
INDOOR
RSEP2S50N - NG Only
The clearance to combustible material represents the minimum distance that must be main-
tained between the outer heater surface and a nearby surface. The stated clearance to com-
bustibles represents a surface temperature of 90F° (50C°) above indoor room temperature.
It is the installer's responsibility to ensure that building materials with a low heat tolerance
which may degrade at lower temperatures are protected to prevent degradation. Examples of
low heat tolerance materials include awnings, vinyl siding, fabrics, some plastics, filmy materials, etc.
Table 4: INDOOR - SUGGESTED MOUNTING HEIGHT FOR COMFORT
MOUNTING
PARAMETERS ***
Mounting angle
Suggested height above deck/floor
SE+ Series Infrared Gas Heater Installation and Operation Manual
MODEL NO
Horizontal
30° Angle
A
S
T
8"
10"
12.5"
10.5" 14.5" 12.5"
24"
33"
24"
MODEL
RSEP1S25X
23,000 Btuh
Horizontal
MAX. 30
9' 0"
9' 0"
10
Under Ends
B
F
U
2.5"
14"
60"
2.5"
26"
60"
24"
78"
78"
MODEL
RSEP1S35X
35,000 Btuh
0
Horizontal
MAX. 30
10' 0"
10' 0"
E
4"
6"
24"
0