Modbus Application Settings - Siemens SITRANS F Operating Instructions Manual

Communication modules modbus rtu rs485
Hide thumbs Also See for SITRANS F:
Table of Contents

Advertisement

MODBUS
MODBUS
register
address
4:00530
529
4:00531
530
A.3

MODBUS application settings

Table A- 4
Slave ID
MODBUS
MODBUS
register
address
4:00601
600
4:00602
601
4:00603
602
4:00604
603
4:00606
605
4:00607
606
4:00608
607
4:00614
613
4:00623
622
Modbus RTU RS485
Operating Instructions, 06/2010, A5E00753974-04
No. of bytes Data type
2
Byte
2
Byte
No. of bytes Data type
2
Byte
2
Byte
2
Byte
3
Byte array
2
Word
2
Word
12
String
18
String
12
String
A.3 MODBUS application settings
Description
Baudrate
0 = 1200
1 = 2400
2 = 4800
3 = 9600 R/W
4 = 19200
5 = 38400
6 = 57600
7 = 76800
8 = 115200
Parity/framing
0 = 8, E, 1
1 = 8, O, 1
2 = 8, N, 2
3 = 8, N, 1
Description
Slave ID:
0x2A = Siemens
Run indicator:
0x00 = not running
0xFF = running
Product code
24 = MAG 6000
25 = MASS 6000
Capability bits
Flowmeter revision (e.g. 0x0201 =
v2.01)
MODBUS revision (e.g. 0x0201 =
v2.01)
Manufacturer name
Product name
MODBUS module name
Modbus holding registers
Read / write
R/W
R/W
Read / write
R
R
R
R
R
R
R
R
R