Totalizer - Siemens SITRANS F Operating Instructions Manual

Communication modules modbus rtu rs485
Hide thumbs Also See for SITRANS F:
Table of Contents

Advertisement

Modbus holding registers
A.5 Totalizer
MODBUS
MODBUS
register
address
4:02031
2030
4:02032
2031
4:02033
2032
4:02034
2033
4:02036
2035
4:02037
2036
4:02039
2038
A.5

Totalizer

Table A- 10
Totalizer, MAG 6000
MODBUS
MODBUS
register
address
4:02102
2101
4:02104
2103
42
No. of bytes Data type
2
Byte
2
Byte
2
Byte
4
Float
2
Word
4
Float
4
Float
No. of bytes Data type
2
Byte
2
Byte
Description
Noise filter:
1 = min.
2
3
4
5 = max.
Error level:
1 = Warning
2 = Permanent
3 = Fatal
Zero adjust mode:
0 = Auto
1 = Manual
Manual zero adjust (kg/s)
Zero adjust time (s)
Zero sigma (kg/s)
Zero sigma limit (kg/s)
Description
Totalizer 1 direction:
0 = Reverse
1 = Forward
2 = Net
Totalizer 2 direction:
0 = Reverse
1 = Forward R/W
2 = Net
Operating Instructions, 06/2010, A5E00753974-04
Read / write
R/W
R/W
R/W
R/W
R/W
R
R/W
Read / write
R/W
R/W
Modbus RTU RS485