Calibration Of Supervised Outputs (H5/A1) - Panasonic EBL512 Operating Instructions Manual

Fire alarm system ebl512 v2.3.x
Hide thumbs Also See for EBL512:
Table of Contents

Advertisement

Panasonic Electric Works Fire & Security Technology Europe AB
MEW00748
27.2
Action
"Access"
"A"
Rev: 1

Calibration of supervised outputs (H5/A1)

The voltage outputs (S0-S3) in each control unit are supervised
(monitored), as well as the outputs (0-3) in each output unit type 2262
and 2263.
When all alarm devices (sounders, etc.) have been connected,
including required resistors
calibration has to be done.
Function: If the actual value differs from the calibrated value ± a
small tolerance or if the calibrated value is outside the calibration
range 4K7 – 50K
NOTE!
Each output's logic is programmable via Win512, i.e. normally low
(default) or normally high (24V) but during the calibration the outputs
will automatically be low, i.e. a normally high output will be low
during the calibration (a few seconds).
Text in display
Calibration of supervised outputs
Calibration in progress
Please wait......
Calibration of supervised outputs
NOTE! After the calibration it is recommended do a "Safe shutdown
of the control unit" (see menu H8/S8). This will save the SSW data
(e.g. the calibration values) in a Flash ROM (see page 69).
83
An end-of-line resistor (33K) in the last unit or a resistor (33K) in up to
five units.
84
Only valid for the c.i.e. outputs S0-S3.
Operating Instructions Fire alarm system EBL512 V2.3.x
83
and when the SSD download is ready, a
84
, a fault will be generated.
ACCEPT? A1
ACCEPT? A1
105
Comments
According to chapter
"Access code for service
(H5)", see page 104.
Calibration is ready.
Scroll or press "Return" to
H5. Scroll or press
"Return" to log off.