INTRODUCTION

Gate Access (Wired)

Disconnect power BEFORE making electrical connections. Below is an example of a wiring setup for gate access. Gate access can be
wired to Door 1 or 2 on the Door Board. LiftMaster
instead of using a wired connection (refer to the following page).
RFID ANTENNA
with Wiegand output
Power for RFID ANTENNA
(Not Provided)
DO NOT use the power
supply for the controller
STATUS
(Not applicable for wireless gate operator connections.)
GATE OPERATOR
(connect to Aux Closed Limit switch -
refer to gate operator manual)
EOL (End of Line)
Resistor (1k ohm)
PRIMARY RELAY
GATE OPERATOR
LiftMaster
®
Security+ 2.0
®
gate
operators can be programmed
to communicate wirelessly
instead of using a wired
connection. Refer to the
following page.
*AUXILIARY RELAY
MAGLOCK
Use 18-22 AWG
For DC Power:
Install a 1N4005
diode or equivalent
PRE-INSTALL
Security+ 2.0
®
WIEGAND
KEYPAD
OR
EXTERNAL FREE EXIT
EXIT
COMMON
For AC Power:
Install a Siemens S10K30MOV
(Metal Oxide Varistor) (provided)
or equivalent
NORMALLY CLOSED
COMMON
+
Power for Maglock
(Not Provided)
DO NOT use the power
supply for the controller
INSTALL
gate operators can also be programmed to communicate wirelessly
®
READER
OR
NOTE: For KPR2000
keypad, wire the pink and
black (ground) wires together.
REQUEST TO EXIT
PUSH
LOOP DETECTOR
BUTTON
OR
NORMALLY CLOSED
AUXILIARY RELAY
Low
Voltage
Power
Supply
Isolation
Relay
NOTE: DO NOT run
high voltage power
within the CAPXM
enclosure.
COMMON
NORMALLY OPEN
17
NETWORK
ACCESS CONTROL
NOTE: The length of the unshielded
wires should be kept to a minimum to
avoid electrical noise.
REQUEST TO EXIT
GROUND
STATUS
NORMALLY OPEN
COMMON
NORMALLY OPEN
COMMON
LIGHT
DO NOT INSTALL THE
SYSTEM IN THE FAIL
LOAD
SECURE MODE UNLESS
LINE
PERMITTED BY THE LOCAL
AUTHORITY HAVING
JURISDICTION. Doing so may
OR
cause interference with the
operation of panic hardware.
ALARM BYPASS
* NOTE: MAGLOCK and ALARM
BYPASS not evaluated by UL.
DOOR 1 or 2