Detailed Transmitter Setup - Emerson Rosemount 2088 Reference Manual

Pressure transmitter
Hide thumbs Also See for Rosemount 2088:
Table of Contents

Advertisement

Configuration
April 2021
2.9.2
Configuring LCD display with AMS Device Manager
Procedure
1. Right select on the device and select Configure.
2. Select Manual Setup, select the Display tab.
3. Select desired display options and click Send.
2.9.3
Configuring LCD display with a LOI
Refer to
Figure 2-13: Display with LOI
2.10

Detailed transmitter setup

2.10.1
Configuring alarm and saturation levels
In normal operation, the transmitter will drive the output in response to pressure from the
lower to upper saturation points. If the pressure goes outside the sensor limits, or if the
output would be beyond the saturation points, the output will be limited to the associated
saturation point.
The transmitter automatically and continuously performs self-diagnostic routines. If the
self-diagnostic routines detect a failure, the transmitter drives the output to configured
alarm and value based on the position of the alarm switch. See
Table 2-5: Rosemount Alarm and Saturation Values
Level
Low
High
Table 2-6: NAMUR-Compliant Alarm and Saturation Values
Level
Low
High
26
Figure 2-13
for LCD display configuration using a LOI.
VIEW CONFIG
ZERO TRIM
UNITS
RERANGE
LOOP TEST
DISPLAY
EXTENDED MENU
EXIT MENU
4–20 mA (1–5 Vdc) saturation
3.90 mA (0.97 V)
20.80 mA (5.20 V)
4–20 mA (1–5 Vdc) saturation
3.80 mA (0.95 V)
20.50 mA (5.13 V)
Rosemount 2088, 2090P, and 2090F Pressure Transmitter Reference Manual
Reference Manual
00809-0100-4108
DISPLAY
PRESS (on/off)
SCALED (on/off)
TEMP (on/off)
%RANGE (on/off)
ANALOG (on/off)
STRTUP (on/off)
BACK TO MENU
EXIT MENU
Setting transmitter
4–20 mA (1–5 Vdc alarm
≤ 3.75 mA (0.95 V)
≥ 21.75 mA (5.40 V)
4–20 mA (1–5 Vdc) alarm
≤ 3.60 mA (0.90 V) (.90 –.95 V)
≥22.50 mA (5.63 V) (5.05 –5.75 V)
alarm.

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rosemount 2090pRosemount 2090f

Table of Contents