Specifications - Parker A Series Installation & Service Instructions Manual

Isysnet 24 vdc output module
Table of Contents

Advertisement

isysNet 24 VDC Output Modules, Series A

Specifications -

Following are specifications for the digital output modules.
Digital Output Modules
Outputs per Module
Voltage Drop, On-State Output, Maximum
Voltage, Off-State Output, Maximum
Voltage, On-State Output,
Maximum
Minimum
Nominal
Current Leakage, Off-State Output, Maximum
Current, On-State Output Minimum
Output Current Rating
Output Delay Time OFF to ON, Maximum
Output Delay Time, ON to OFF, Maximum
Output Point Density
Output Surge Current, Maximum
External DC Power Supply Current
External DC Power Supply Voltage Range
External DC Power Supply Voltage Nominal
Keyswitch Position
LED Indicators
PointBus Current, Maximum
Power Dissipation, Maximum
Thermal Dissipation, Maximum
Isolation Voltage
(continuous-voltage withstand rating)
Dimensions (includes I/O module
and mounting base)
Operating Temperature
Storage Temperature
Relative Humidity
Shock
Vibration
ESD Immunity
Radiated RF Immunity
EFT/B Immunity
Surge Transient Immunity
Conducted RF Immunity
Emissions
Enclosure Type Rating
Mounting Base Screw Torque
Wiring Category
2
Weight Imperial (Metric)
Certifications:
(when product is marked)
1. OFF to ON or ON to OFF delay is time from a valid output "on" or "off" signal to output energization or de-energization.
2. Use this Conductor Category information for planning conductor routing. Refer to Publication E115P, "Industrial Automation Wiring and Grounding Guidelines".
8 (1 Group of 8) Non-isolated, Sourcing
0.2VDC (Sourcing Modules)
0.7VDC (Sinking Module)
28.8VDC
28.8VDC
10VDC
24VDC
0.5 mA
1.0 mA Per C hannel
1.0 A Per Channel, Not To Exceed 3.0 A Maximum Per Module
0.1 ms
1
1
0.1 ms
8 or 16
2 A for 10 ms, Repeatable Every 3 Seconds
32 mA
10 to 28.8VDC
24VDC
1
8 orr 16 Yellow/Red Output Status, Logic Side
1 Green/Red Network Status, Logic Side
1 Green/Red Module Status, Logic Side
75 mA @ 5VDC
PSST8M - 2.0W @ 28.8VDC
PSST8M - 6.8 BTU/hr. @ 28.8VDC
50V rms
Tested at 1250VAC rms for 60s
Inches
4.72H x 2.82W x 1.65D
(Millimeters)
(120H x 72W x 42D)
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20 to 60°C (-4 to 140°F)
IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat),
-40 to 85°C (-40 to 185°F)
IEC 60068-2-30 (Test Db, Un-packaged Non-operating Damp Heat):
5 to 95% Non-condensing
IEC60068-2-27 (Test Ea, Unpackaged Shock):
Operating 30g
Non-operating 50g
IEC60068-2-6 (Test Fc, Operating):
5g @ 10 to 500Hz
IEC 61000-4-2:
6kV Contact Discharges
8kV Air Discharges
IEC 61000-4-3:
10V/m with 1kHz Sine-wave 80% AM from 30MHz to 2000MHz
10V/m with 200Hz 50% Pulse 100% AM at 900Mhz
10V/m with 200Hz 50% Pulse 100% AM at 1890Mhz
IEC 61000-4-4: ±3kV at 5kHz on Signal Ports
IEC 61000-4-5: ±1kV Line-line(DM) and ±2kV Line-earth(CM) on Signal Ports
IEC 61000-4-6: 10Vrms with 1kHz Sine-wave 80%AM from 150kHz to 80MHz
CSPR 11: Group 1, Class A
Meets IP65/66/67 (when marked)
#8 Screw, 7.5 in. lbs. in Aluminum, 16 in. lbs. in Steel
1 - on Signal Ports
0.64 lb. (0.29 kg)
c-UL-us
UL Listed Industrial Control Equipment,
certified for US and Canada
CE
European Union 89/336/EEC EMC Directive, compliant with:
EN 61000-6-4; Industrial Emissions
EN 50082-2; Industrial Immunity
EN 61326; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
C- Tick
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11;
Industrial Emissions
16 (1 Group of 16) Non-isolated, Sourcing
8
E107P

Advertisement

Table of Contents
loading

This manual is also suitable for:

Psst8m23aPsst8m12aPsst8m8aPsst16m23aPsst16025aPsst16m12a

Table of Contents