isysNet 24 VDC Output Modules, Series A
If your RSLogic 5000 is Version 13.X:
• Choose the equivalent Rockwell Automation module from the list
of modules.
Equivalent Rockwell Automation
isysNet Modules
PSST8M8A
PSST8M12A
PSST8M23A
* 1738-OB8EM23 profile will be available in RSLogix 5000 v15.
To use 1738-OB8EM23 in RSLogix 5000 v13, choose
1738-OB8EM12 profile and disable keying.
• Enter a name (optional), slot number, and communication format.
Make sure to choose Compatible Module for Electronic Keying
setting.
• Choose Next to set RPI.
• Choose Finish. Notice that the output module is now under the
I/O configuration
Equivalent Rockwell Automation
isysNet Modules
PSST16M23A
PSST16D25A
PSST16M12A
1738 ArmorPoint Modules
1738-OB8EM8
1738-OB8EM12
1738-OB8EM23*
1738 ArmorPoint Modules
1738-OB16E19M23
1738-OB16E25DS
1738-OB16EM12

Troubleshoot With the Indicators

PSST8M12A
Indication
Probable Cause
Module Status
Off
No power applied to device
Green
Device operating normally
Flashing Green
Device needs commissioning due to
missing, incomplete, or incorrect
configuration
Flashing Red
Recoverable fault
Red
Unrecoverable fault -
may require device replacement
Flashing Red/Green
Device is in self-test
Indication
Probable Cause
Network Status
Off
Device is not on line:
- Device has not completed
- Device not powered - check module
Flashing Green
Device is on line but has no
connections in the established state.
Green
Device is on line and has
connections in the established state.
Flashing Red
One or more I/O connections in
timed-out state.
Red
Critical link failure - failed
communication device. Device
detected error that prevents it from
communicating on the network.
Flashing Red/Green
Communication faulted device - the
device has detected a network access
error and is in communication faulted
state. Device has received and accepted
an Identity Communication Faulted
Request - long protocol message.
Indication
Probable Cause
I/O Status
Off
Output is inactive
Yellow
Output is active and under control
Flashing Red
Open circuit detection. No load.
(Off-State only)
Red
Short circuit detected. (On-State only)
7
Module Status Indicator
Network Status Indicator
I/O Status Indicators
dup_MAC-id test.
status indicator.
E107P