Digital Outputs - Trane PolyTherm ARTC-SVX005A-EN Installation, Operation And Maintenance Manual

Simultaneous chiller/heater
Table of Contents

Advertisement

Digital LEDs
There is an LED for each digital input that indicates its
current state. For all inputs, the color of the LED signifies
its current state:
Figure 22. Digital inputs
DI1 Remote On/Off
This activates a module on or off via digital input. If the
master digital on-off input is enabled, toggling the DI1 on
the master module will turn the entire chiller/heater on or
off.
DI2, DI3, and DI4
These show the states of the evaporator, condenser, or
source flow switches. If the digital input for a switch
indicates closed, flow is present. If the digital input for a
switch indicates open, flow is absent.
DI7 and DI8
These show the discharge and suction pressure switches.
If the digital input for a switch indicates closed, the
pressure is in the normal range. If the digital input for a
switch indicates open, the pressure is exceeding normal
range threshold (that is, faulty state).
DI9 Phase Monitor
This is feedback for the three-phase power supply
protection feature. If the digital input for this switch
indicates closed, there are no power supply issues. If the
digital input for this switch indicates open, a power supply
failure has been detected.
If the master phase monitor is enabled, the common
power supply protection module is active for the chiller/
heater. Failure of the phase monitor will affect all modules
in the chiller/heater. In this case, digital input is optional for
the slave modules.

Digital Outputs

There is an LED for each digital output which shows its
current state.
ARTC-SVX005A-EN
Green LED This digital input is energized, the
connected device is closed.
Gray LED This digital input is de-energized, the
connected device is open.
DO1, DO2 Comp On/Off
This digital output turns a compressor on and off.
DO3 Liq Line Solenoid 'E'
This digital output energizes and de-energizes the liquid
line solenoid valve E.
DO4 Liq Line Solenoid 'S'
This digital output energizes and de-energizes the liquid
line solenoid valve S.
DO6, DO7, DO8, DO9
Valve D1, D2, S1, S2. Used to command refrigerant valves
open / closed. Green LED - valve is commanded open.
Grey LED - valve is commanded closed.
DO10 General Alarm
This digital output energizes when any of the following
alarms occur:
An alarm that shuts down and locks out compressor 1
or 2.
An alarm that shuts down and locks out the entire
module.
DO11 Panel Heater / Fan (optional)
This is the digital output is used when temperature control
inside control panel is required (identical to AI9).
Operating Procedures
41