Trane PolyTherm ARTC-SVX005A-EN Installation, Operation And Maintenance Manual page 25

Simultaneous chiller/heater
Table of Contents

Advertisement

In cooling mode, the diverting valves direct the load chilled
fluid to the evaporator and simultaneously direct the
source/sink fluid to the source/sink brazed plate heat
exchanger operating as a condenser.
Figure 10.
50 and 60-ton PolyTherm dimensions
In simultaneous heating and cooling mode, the diverting
valves direct the load heating fluid to the condenser and
the load cooling fluid to the evaporator.
Electronic valves on the brazed plate source/sink heat
exchanger outlet modulate to control refrigeration head
pressure. Electronic valves on the evaporator and
condenser outlet also allow for variable flow. See
p. 24
and
Figure 10, p.
25.
ARTC-SVX005A-EN
In heating mode, the diverting valves direct the load
heating fluid to the condenser and the source/sink fluid to
the source/sink brazed plate heat exchanger as refrigerant
has been redirected such that it operates as an evaporator.
Figure 9,
Operating Principles
25