3.9 ARxxx-MF / VRxxx-MF Reader

3.9.1 RIM Settings

3.9.2 Required Settings for Reading the UID Number of a
A6V11164550
It is recommended that the ARxxS-MF/VRxxx-MF OSDP reader technology be
selected if the UID number of a MIFARE card has to be read. The corresponding
Base Card Technology that has to be licensed is the Siemens Readers clock/data
RS485.
If Sector/Block information of a MIFARE Classic or/and Application ID of a MIFARE
DESFire card has to be read, select "Siemens Mifare Facility". This is the
corresponding Reader Technology if MIFARE cards are encoded with SiPass
integrated.
More details can be found inside the training documentation.
MIFARE Card
1. Open the FLN configuration and navigate to the RIM (DRI/ERI) which the new
ARxxx-MF/ VRxxx-MF reader is connected to.
2. Download the new firmware to the corresponding RIM.
3. Select ARxxx-MF/ VRxxx-MF OSDP reader technology in the
Tab.
4. Set the option Reader Tamper Auto-Reset.
 Note: The ARxxx-MF/ VRxxx-MF reader is equipped with a Tamper
contact. For a higher security level the Reader Tamper Auto-Reset setting
should be set to No. If this option is chosen and a tamper event occurs, the
operator must reset the Tamper manually from the
5. Save the configuration.
FLN Devices and Readers
ARxxx-MF / VRxxx-MF Reader
Configuration
Component
3
dialog.
33 | 38