Siemens SiPass integrated Controller And Device Installation Manual

Hide thumbs Also See for SiPass integrated:
Table of Contents

Advertisement

Quick Links

Access Control
SiPass integrated
Controller and Device Installation Guide
MP 2.80
A6V11164550
Smart Infrastructure
07.09.2020

Advertisement

Table of Contents
loading

Summary of Contents for Siemens SiPass integrated

  • Page 1 Access Control SiPass integrated Controller and Device Installation Guide MP 2.80 A6V11164550 Smart Infrastructure 07.09.2020...
  • Page 2 Edition: 07.09.2020 Document ID: A6V11164550 © Siemens Switzerland Ltd, 2020 2 | 38 A6V11164550...
  • Page 3: Table Of Contents

    Firmware Configuration Tools ACC USB Client Application Table of Contents Firmware Configuration Tools ..............5 ACC USB Client Application ................5 1.1.1 Installing the USB RNDIS Driver ............. 5 1.1.2 Configuring the ACC USB Client Application ........6 ACC and FLN Field Service Network Tool ............7 1.2.1 Installation ..................
  • Page 4 Firmware Configuration Tools ACC USB Client Application 2.3.3.8 Wiegand Reader Turnstile, Dual Door Contact Configuration ........23 2.3.4 Extension Interfaces ..............24 2.3.4.1 Extension Option ............24 2.3.4.2 Aperio Wireless Doors Extension Option ....... 24 2.3.5 Power Monitoring Limits..............24 2.3.6 Factory Reset Button ..............
  • Page 5: Firmware Configuration Tools

    ● USB A-B Cable AccG2UsbClient ● application for the Windows host (available under Tools\ACC- G2_USB_Tool\ in SiPass integrated installation bundle) ● USB RNDIS driver (available under Tools\ACC-G2_USB_Tool\RNDIS_Driver\ in SiPass integrated installation bundle) 1.1.1 Installing the USB RNDIS Driver Ensure that the power for the ACC controller unit is connected and ON.
  • Page 6: Configuring The Acc Usb Client Application

     If you are using MP2.70 SP1 (or later) version, when you change the SIEMENS user password, the password for the “root” user for a SSH connection will also be changed to the same password that was set for the SIEMENS user.
  • Page 7: Acc And Fln Field Service Network Tool

    The ACC and FLN Field Service Tool has been designed to assist in the installation of Field Level Network devices for use with the SiPass integrated Access Control and Security System. This includes: ●...
  • Page 8: Network Discovery For Access Controllers

    Firmware Configuration Tools ACC and FLN Field Service Network Tool 1.2.3 Network Discovery for Access Controllers It is possible to configure Access Controllers via Ethernet, without prior configuration of any settings. The ACC and FLN Field Service Tool uses UDP Broadcasts to identify ACC controllers that have their Quickstart feature enabled.
  • Page 9: Enhanced Fln Communication

    ACC and FLN Field Service Network Tool 1.2.4 Enhanced FLN Communication With SiPass integrated MP 2.70 SP1 onwards, the standard communication of firmware uses added security measures. You can add a device with Legacy Firmware to an existing FLN bus that contains devices with the new Standard Communication.
  • Page 10: Built-In Acc Tools

    Console command. If both PIN and Telnet passwords are lost, then the device must be returned to the manufacturer or Siemens. If you changed the PIN using SiPass integrated MP2.7, install an earlier version of the ACC-Lite firmware, then again re-install MP2.7, you must logon with the PIN that was previously set (because the PIN has already been changed using the MP2.7 build, setting a new PIN is not required again).
  • Page 11: Access Controllers

    If the controller is already running the latest platform version, update by using the Initialize System Image Download option in the dialog of SiPass integrated to download the firmware application image. ● Subject to the network load, download is expected to take a few minutes.
  • Page 12: Updating Controller Platform Via Firmware Download

    2.1.2 Updating Controller Platform via Firmware Download Note: Current version of the controller’s platform and application are shown in the Initialize System dialog of SiPass integrated. ● In case it is required to control the timing of the downtime caused by the...
  • Page 13 Application fails to start after System Update, the system will automatically revert to the previous state. ● Recovery from corrupted database: If ACC Application fails while loading the database, the database will be deleted and initialization from SiPass integrated will be required. A6V11164550 13 | 38...
  • Page 14: Ac5102 (Acc-G2)

    Access Controllers AC5102 (ACC-G2) 2.2 AC5102 (ACC-G2) AC5102 Hardware Technical Manual See the in the SiPass integrated software bundle. 2.2.1 Configuring the AC5102 Controller using USB Client Application See section ACC-G2 USB Client Application for more details. 2.2.2 Network Discovery of AC5102 See section ACC and FLN Field Service Network Tool for details.
  • Page 15: Rs232 Mode On Fln 2 And Fln 3

    A magnifying glass and a small screwdriver are useful for setting the EOL dip switches. AC5102 Technical Manual See the in the SiPass integrated software bundle for more information. Note: Disregard connections for FLN 2 & 3 shown in Section “Bus Termination of AC5102 Technical Manual the FLNs”...
  • Page 16: Recovering A Non-Responsive Board

    Access Controllers AC5102 (ACC-G2) 2.2.6 Recovering a Non-responsive Board See section Restoring/Updating Platform via SD Card [➙ 16] for details. 2.2.7 ACC-G2 Firmware Update Procedures See section Common Firmware Update Procedure [➙ 11] for details. 2.2.8 Restoring/Updating Platform via SD Card 2.2.8.1 Preparing the SD Card Before you begin, prepare the SD Card by following the steps below: 1.
  • Page 17: Sd-Card Upgrade Procedure

    Access Controllers AC5102 (ACC-G2) 2.2.8.2 SD-Card Upgrade Procedure Note: In case of SD Card update, the database configuration and system settings will be lost. To perform the SD-Card upgrade, the following steps should be taken -: 1. Having written the SD Card, power down the ACC-G2 and insert the SD Card into the ACC SD-Card slot –...
  • Page 18: Sd Card Update Troubleshooting

    Access Controllers AC5102 (ACC-G2) 2.2.8.3 SD Card Update Troubleshooting For SD Card Updates, the ACC-G2 only supports non-HC type SD Cards. This means SD Cards in the range of 512MB to 2GB only can be used. 1. There is an issue with using 1GB and 2GB SD Cards on the older ACCs with the 32kB EEPROM - when loaded with a CCP2 update image, the cards are not recognized by RomBOOT.
  • Page 19: Acc-Ap

    Access Controllers ACC-AP 2.3 ACC-AP 2.3.1 General Information The IP-based AP door controller offers the latest technology, better cost- effectiveness, and easy installation. It supports: ● 2 OSDP Readers: Controller for one or 2 doors (depending on configuration) ● 4 Monitored or Unmonitored Inputs ●...
  • Page 20: Onboard Door (Drie) Interfaces

    Access Controllers ACC-AP 2.3.3 Onboard Door (DRIe) Interfaces NOTICE IMPORTANT Before connecting the Wiegand readers to the ACC AP DRIe, the End of Line (EOL) jumper for the readers MUST BE DISABLED. If the EOL jumpers are On (default setting), the Wiegand reader will not work. 2.3.3.1 Dual OSDP Reader Door Configuration Label on AP Controller SiPass Point Function...
  • Page 21: Osdp Reader Turnstile, Single Door Contact Configuration

    Access Controllers ACC-AP 2.3.3.3 OSDP Reader Turnstile, Single Door Contact Configuration Label on AP Controller SiPass Point Function IN 1 Door 1 REX IN 2 Door 1 D/C IN 3 Door 2 REX IN 4 In 1 RLY 1 Door 1 LK RLY 2 Door 2 LK OUT 1...
  • Page 22: Dual Wiegand Reader Door Configuration

    Access Controllers ACC-AP 2.3.3.5 Dual Wiegand Reader Door Configuration Label on AP Controller SiPass Point Function IN 1 IN 2 IN 3 In 1 In case of ACC-APM 12V/24V PSU Kit, the pre-wiring is already done for power monitoring. IN 4 In 2 In case of ACC-APM 12V/24V PSU Kit, the pre-wiring is already done for cabinet tamper.
  • Page 23: Wiegand Reader Turnstile, Single Door Contact Configuration

    Access Controllers ACC-AP 2.3.3.7 Wiegand Reader Turnstile, Single Door Contact Configuration Label on AP Controller SiPass Point Function IN 1 Door 1 REX IN 2 Door 1 D/C IN 3 Door 2 REX IN 4 In 1 RLY 1 Door 1 LK RLY 2 Door 2 LK OUT 1...
  • Page 24: Extension Interfaces

    Access Controllers ACC-AP 2.3.4 Extension Interfaces 2.3.4.1 Extension Option Label on AP Controller SiPass Point Function FLN 2 COMMS1 for MFI*, IAT and I/O devices (8IO, IPM, OPM) *See section Multi-Function Interface (MFI) [➙ 35] for more information. COMMS2 Not Used 2.3.4.2 Aperio Wireless Doors Extension Option Label on AP Controller SiPass Point Function...
  • Page 25: Restoring/Updating Platform Via Sd Card

    Once the controller is powered up, the network settings must be configured as described in Section Configuring the ACC USB Client Application [➙ 5]. The AP Controller is now set up and can be connected to SiPass integrated. A6V11164550 25 | 38...
  • Page 26: Platform Upgrade Via Firmware Download

    Update failed. Retry SD-Card update 2.3.9.2 During ACC-Application (Run-Time) LED Indication Description Controller is starting up ORANGE Application running GREEN Application running, connected with SiPass integrated OFF (Dark) Application not running. (This can occur during a Firmware upgrade.) 26 | 38 A6V11164550...
  • Page 27: 4101-3 (Acc-Granta)

    The default network settings are: IP Address : 192.168.1.250 Subnet Mask : 255.255.255.0 Default login credentials: SIEMENS/spirit All other settings are zeroed (including the SiPass host address) and modem configuration is disabled. The SSH server is re-enabled as well as the Telnet server.
  • Page 28: Recovering A Non-Responsive Board

    Access Controllers 4101-3 (ACC-Granta) 2.4.4 Recovering a Non-responsive Board Try the X992 jumper option first. If this does not work, it is possible to restore a board completely to factory settings. Note: This requires that the cover be removed from the Controller and a SD card. The SD card must be a plain SD card, 2GBytes or less.
  • Page 29: Network Security

    Access Controllers 4101-3 (ACC-Granta) 2.4.5 Network Security The ACC-GRANTA uses Linux as an operating system, which provides both an increased level of security and reliability, but also requires some extra care in security. Summary: disable both SSH and telnet for maximum security, and set a root password.
  • Page 30: Ac5100 (Acc-G1)

    (The default IP address is now: 192.168.1.250) 3. Reset the ACC. 4. Login via the DIAG port. Default login credentials are: SIEMENS/spirit 5. Reset the network settings. 6. Then upgrade back to MP 2.70, login and change the password when asked.
  • Page 31: Ac5200 (Acc-Lite)

    Firmware downloads are done from the SiPass integrated software. This process is the same as downloading firmware for an ACC. Before you begin: The AC5200 must be created in the SiPass integrated database and be com- municating To download firmware to the AC5200: 1.
  • Page 32: Fln Devices And Readers

    See the appropriate User Manual for more information. 3.8 OSDP Reader Devices With SiPass integrated MP2.76 onward, you get the support for connecting OSDP Reader Devices directly to controller FLN (for ACC-G1 and ACC-G2 only). The OSDP Reader devices are programmed using...
  • Page 33: Arxxx-Mf / Vrxxx-Mf Reader

    It is recommended that the ARxxS-MF/VRxxx-MF OSDP reader technology be selected if the UID number of a MIFARE card has to be read. The corresponding Base Card Technology that has to be licensed is the Siemens Readers clock/data RS485. If Sector/Block information of a MIFARE Classic or/and Application ID of a MIFARE DESFire card has to be read, select “Siemens Mifare Facility”.
  • Page 34: Wiegand Reader On Acc-Ap

    – SaltoWiegand34 – EricssonWiegand – Europlex34Bit – Remec37Bit See the documentation in SiPass integrated software bundle for more information on the following topics: ● Wiegand Readers connections with ACC-AP ACC-AP Technical Manual – See the ● Configuration ofWiegand Readers with ACC-AP through SiPass integrated...
  • Page 35: Multi-Function Interface (Mfi)

    FLN Devices and Readers Multi-Function Interface (MFI) 3.11 Multi-Function Interface (MFI) With release MP2.80 onward, SiPass integrated offers you the Multi-Function Interface (MFI) that adds-on to the powerful functionality of the ACC-AP door controller. ACC FLN Bus It can be added under ACC-AP (FLN 2 with...
  • Page 36: Aperio Wireless Lock Technology

    FLN Devices and Readers Aperio Wireless Lock Technology 3.12 Aperio Wireless Lock Technology With the enhancements made in SiPass integrated MP2.76 SP1 onward, the Aperio Wireless Lock technology is expanded to support multiple Aperio Hubs ® connected to one ACC-AP through the Aperio FLN Bus (RS485 communication channel).
  • Page 37: Connecting Aperio Hub With Acc-Ap

    3.13 Help and Documentation The hardware for Aperio Wireless Technology and Multi Function Interface (MFI) is not supplied by Siemens. However, to help you quickly setup everything, SiPass integrated documentation gives you the required support information sourced from the device manufacturer. The standard SiPass firmware documentation also helps you at places during the whole process.
  • Page 38 Issued by Siemens Switzerland Ltd Smart Infrastructure Global Headquarters Theilerstrasse 1a CH-6300 Zug +41 58 724 2424 www.siemens.com/buildingtechnologies © Siemens Switzerland Ltd, 2020 Technical specifications and availability subject to change without notice. A6V11164550...

Table of Contents