A6V11164550
More about Platform Update:
Platform image is a large file that contains complete Operating System
distribution and it will take at least 30 minutes to download to the ACC.
However, the ACC will remain fully operational during the download phase.
After ACC Platform image has been successfully written to the flash memory,
Download succeeded. ACC flash programming OK
the "
displayed in the audit trail.
If auto update is enabled, the "
ACC will reset after completion!
and the ACC will restart to initiate the platform upgrade.
During platform installation, the controller is expected to reboot at least twice.
Database configuration and system settings will be kept. Overall downtime is
expected to be between 1 and 10 minutes, depending on the size and
fragmentation of database.
Recovery from unsuccessful System Update: If System Update fails or ACC
Application fails to start after System Update, the system will automatically
revert to the previous state.
Recovery from corrupted database: If ACC Application fails while loading the
database, the database will be deleted and initialization from SiPass integrated
will be required.
Access Controllers
Common Firmware Update Procedure
Upgrade of ACC Platform has been initiated.
" message will be displayed in the audit trail,
2
" message will be