3.1.3

With Heat Shield AC02762 and Lowered Ceiling

To reduce the clearances of an appliance using a single wall pipe connector, the use of a heat
shield certified with the single wall pipe connector to be used as close as 6" from combustible
materials must be used. Only in this case, the same clearances as a certified double wall pipe
connector can be used . Refer to the booklet present in the screen options to obtain the dimensions
to be respected.
APPLIANCE CLEARANCES WITH DOUBLE
WALL PIPE CONNECTOR
Canada
2 ½" (64 mm)
A
2 ½" (64 mm)
B
2 ½" (64 mm)
C
72" (1829 mm)
L
DISTANCES
WITH DOUBLE WALL PIPE CONNECTOR
Canada
5 ¾" (146 mm)
D
8 ¼" (210 mm)
E
9" (229 mm)
F
A
D
B
E
CAN
48"
122 cm
If the clearance reduction is on the same side as the door handle, position the stove at
a minimum of 6 inches from the side wall (clearance B), otherwise it may be located at
the clearance shown in the table above.
18
The pipe distances listed in this table refer to the distances obtained when the stove is installed in accordance with the appliance clearances
above mentioned.
Installation and Operation Manual - Escape 1200
USA
2 ½" (64 mm)
2 ½" (64 mm)
2 ½" (64 mm)
72" (1829 mm)
FROM PIPE CONNECTOR
18
USA
5 ¾" (146 mm)
8 ¼" (210 mm)
9" (229 mm)
48"
US
Flush
36"
92 cm
Ve
Ho
F
F
L
C
Page 15