Ma Interface; Alarm Relay - Beko DRYPOINT M eco control DEC 1-30S Original Installation And Operation Manual

Drying system
Table of Contents

Advertisement

EN

2.6. 4 ... 20 mA interface

The drying system is equipped with a 4 ... 20 mA interface via which the currently measured pressure dew point can be
issued (irrespective of operating mode).
4 mA ≙ -48 °C
20 mA ≙ +25 °C
Output value in case of error: 24 mA
Increments: 0.5 °C

2.7. Alarm relay

The drying system is equipped with an alarm relay via which an error signal can be issued.  There will not be a differentiation 
here between various types of errors.
Error list:
Sensor fault (Refer to 9.1.2)
Exceeding the permissible deviation for degree of drying (Refer to 9.1.3)
Failure of the voltage supply (Refer to 9.1.1)
DRYPOINT
M eco control
®
Installation and operating manual
15