Function/Configuration
SITRANS LVL200S l RELAY (DPDT)
6 Set up
6.1 In general
The numbers in brackets refer to the following illustrations.
In the basic setting, products with a density > 0.7 g/cm³
(0.025 lbs/in³) can be detected. For products with lower
density, you have to set the switch to > 0.5 g/cm³ (0.018 lbs/
in³).
On the electronics module you will find the following indicating
and adjustment elements:
Control lamp for indication of the switching condition (1)
l
DIL switch for mode adjustment - A/B (2)
l
DIL switch for sensitivity adjustment (3)
l
Note:
For test purposes, immerse the tuning fork of SITRANS
LVL200S always in liquids. Do not test the function of
SITRANS LVL200S with the hand. This can damage the
sensor.
6.2 Adjustment elements
Fig. 10: Oscillator SWE60R - Relay output
1
Signal lamp (LED)
2
DIL switch for mode adjustment
3
DIL switch for sensitivity adjustment
Set up
1
2
3
19