Stroking Time Selection In Closing - Emerson Bettis SCE300 Installation, Operation And Maintenance Manual

Table of Contents

Advertisement

Installation and Maintenance Instructions
MAN-02-04-99-0712-EN Rev. 1
NOTE
During the new stroke limit setup, the minimum range between open and close limit
position has to be at least within 45 degrees of the valve position; if the above condition
is violated, the setup will not be successful and stroke limit error alarm will signal (shown
by a red LED blinking). The red LED will continuously flash when the actuator is in setup
functionality (dip switch SW3 in 'on' position) and rotary switches SW4 and SW6 are in one
of the following positions:
a.
b.
c.
d.
The alarm is then reset by:
a.
b.
CAUTION
Actuator configuration must be conducted while the actuator is powered on. Do not touch
any components not required for configuration to avoid injury or damage to equipment.
6.2.8

Stroking Time Selection in Closing

Actuator Configuration
SW4=3 and SW6=0
(stroke limit of open configuration by torque)
SW4=2 and SW6=0
(stroke limit of close configuration by torque)
SW4=1 and SW6=0
(stroke limit of open configuration by position)
SW4=0 and SW6=0
(stroke limit of close configuration by position)
Switching off and on the actuator
Performing a new, correct stroke limit setup in one of the 4 possible combinations.
Enter setup configuration: move switch SW3 to position ON (configuration function)
Move switch SW4 to position 4
Move switch SW6 to positions 4, 6, 8 for the requested stroking time according to
the table below
Push ENTER pushbutton SW5 to confirm
When pushing SW5, the red LED switches on for confirmation
The selected stroking time in closing is now set
Exit setup configuration (move switch SW3 to position 1) or proceed to the
next parameter
Section 6: Actuator Configuration
February 2020
35