Outdoor Installation / Heater Clearances - Pentair MASTERTEMP 200HD Installation And User Manual

Pool and spa heater (for outdoor use only)
Hide thumbs Also See for MASTERTEMP 200HD:
Table of Contents

Advertisement

If installing the heater next to or near an air conditioning unit or a heat pump, allow a minimum of 1000 mm
between the air conditioning unit and the heater.
OUTDOOR INSTALLATION
SIDE VIEW
1500 mm
Window
1500 mm
Exhaust Grill
(Vent)
Building
Figure 15.
Risk of fire and explosion. Do not spray aerosols in the vicinity of the heater while it is in operation. Chemicals should
not be stored near the heater installation. Combustion air can be contaminated by corrosive chemical fumes which
can damage the heater and will void the warranty.
P/N 474131 Rev. M 8/2020
CAUTION
VENTING GUIDELINES
WARNING
1500 mm
1500 mm
1500 mm
Property Line
Air Inlet
Vent Termination:
Must be installed at least 1500 mm away from
the building wall openings, and at the following
distances away from any door, window, or
gravity air inlet.
The heater must also have no obstructions above it.
MasterTemp Pool and Spa Heater
21