Changing The Set Value; Output Delay - Omron H7CR-A Series Manual

Compact 1/16 din counters, four- or six-digit lcd displays
Table of Contents

Advertisement

H7CR
Setting Mode continued
Item
Applicable Counters
Decimal point
H7CR-B, H7CR-SB
H7CR-C, H7CR-SC
H7CR-8, H7CR-11
Scale factor
H7CR-B, H7CR-SB
H7CR-C, H7CR-SC
H7CR-8, H7CR-11
Key protection
H7CR-B, H7CR-SB
level
H7CR-C, H7CR-SC
H7CR-11
Note: Settings changed in the Setting mode are effective only after returning to the Run mode.
EXAMPLES
Run Mode

Changing the Set Value

When changing the set value while the counter is operating, an
output will be produced if the set value ever equals the present
value. To avoid triggering the output, begin by setting a higher
digit to a larger number.
1. Press the DISPLAY key to change the displayed values for
preset 1 and 2 during operation.
2. Change the set value from
250 to 1,250.
Pressing increment keys 1
to 6 advances the
corresponding column
value by 1.
Nonsignificant zeros are
not normally shown on the
set value display.
Description
Determines the position of the
decimal point on the display.
Press the Increment keys 1 to 6 to
move the decimal from left to right.
Used to convert counts to other
units, (e.g., to display millimeters
when each input pulse represents
0.02 mm, input a scale factor
of 0.02). Values from 0.001 to 99.999
are possible. Press the Increment
keys to set the desired value.
Blocks certain keys to prevent
accidental operation. The key
protection level, kP-1 to kP-4,
determines which keys are locked
out when the key protection input
is ON. The locked keys are crossed
out in the diagrams at right.

Output Delay

The following table shows the delay from when the present
value passes the set value until the output is produced. The
delay is the result of output control time, signal transmission
time, relay switching time etc.
Actual measurements in N and K modes:
Control
output
Contact
OUT1,
OUT2
Transistor
OUT1,
OUT2
* The variation in delays is due to different modes and
conditions. For systems where the delay is a problem, take
actual measurements under operating conditions.
24
Setting values
Increment keys 1 to 6 move decimal point.
Increment keys 1 to 5 change the scaling
Increment keys 1 to 4 change key
protection level.
Max. counting
Output
speed
delay*
30 cps
18 to 24 ms
1 kcps
4.7 to 5.8 ms
5 kcps
4.4 to 5.4 ms
30 cps
13.5 to 20 ms
1 kcps
0.59 to 0.81 ms
5 kcps
0.29 to 0.44 ms
H7CR